5407934-UIM-C-1119
72
Johnson Controls Ducted Systems
STATUS
For forced operation, clear any active delay timers shown
on the Status screen. To clear the timer values for the ON,
OFF, CYCLE, and STAGE DELAY timers, tap the screen
area as shown in Figure 39 and hold for 5 seconds. The
Status screen also shows current lockouts. You clear lock-
out timers in the same way. To clear the timer values for the
COOL, AUX HEAT, and HP HEAT lockout timers, tap the
screen area and hold for five seconds.
FIGURE 44:
Status
Status
A1238-001
STATUS
TIMERS (SECONDS):
ON:
OFF:
CYCLE:
STAGE DELAY:
FORCED STAGE UP:
AUTO CHANGE:
FUEL TYPE CHANGE:
0
0
0
0
1695
0
0