background image

M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions

4

Mounting

The M9000-310 and M9000-320 Weather Shield 
Enclosure Kits are shipped from the factory partially 
assembled, with the cover held in place using the four 
cover screws included with the kit. The remainder of 
the parts required for mounting can be found inside the 
enclosure.

Control Damper Applications

Mount the weather shield enclosure onto a control 
damper as follows:

1.

Loosen the four cover screws using a No.1 Phillips 
screwdriver and remove the cover and gasket 
assembly from the enclosure base.

2.

Orient the anti-rotation bracket onto the enclosure 
as illustrated in Figure 3.

Note:

The anti-rotation bracket must be oriented 

properly for the anti-rotation tab to align with the slot on 
the electric actuator.

3.

Secure the anti-rotation bracket to the threaded 
brass inserts of the enclosure base using two 
M3 x 8 mm Phillips screws and M4 washers 
included with the kit. Tighten the Phillips screws to 
a torque of 15 to 20 lb·in (1.7 to 2.3 N·m).

4.

Orient the two mounting brackets onto the 
enclosure base as illustrated in Figure 4.

5.

Secure the mounting brackets to the enclosure 
base using four No. 12-24 x 1/2 in. hex-head 
screws (included with the kit).

Note:

Each hex-head screw should be inserted from 

the inside of the enclosure so that the nitrile patch 
seals the mounting hole in the base.

6.

Install the enclosure and mounting bracket 
assembly onto the damper shaft extension. Orient 
the assembly so that the flanges of the mounting 
brackets are flush with the mounting surface.

7.

Using the mounting brackets as a template, mark 
the mounting hole locations with a ball-peen 
hammer and punch.

8.

Remove the enclosure and mounting bracket 
assembly from the damper shaft extension.

9.

Drill pilot holes at each of the marked spots using a 
drill and a No. 10 drill bit.

10. Reinstall the enclosure and mounting bracket 

assembly onto the damper shaft extension. Orient 
the assembly so that the flanges of the mounting 
brackets are flush with the mounting surface and 
the holes in the mounting brackets align with the 
pilot holes drilled in Step 9.

11. Secure the enclosure and mounting bracket 

assembly to the mounting surface using four 
No. 12-24 x 1/2 in. hex-head screws included with 
the kit. Tighten the hex-head screws to a torque of 
20 to 25 lb·in (2.3 to 2.8 N·m).

IMPORTANT:

Do not overtighten the Phillips 

screws. Overtightening may cause the threaded 
inserts located in the enclosure base to become 
dislodged, resulting in damage to the enclosure.

M9000-320

M9000-310

Anti-Rotation

Bracket

Anti-Rotation

Bracket

F

IG

:r

tb

rk

t

Figure 3: Proper Orientation of the Anti-Rotation 

Bracket

M9000-320

M9000-310

F

IG

:m

n

tb

rk

t

Figure 4: Proper Orientation of the 

Mounting Brackets onto the Enclosure Base

Summary of Contents for M9000-320 Series

Page 1: ...nformation on the M9000 Series Electric Actuators and Valve Linkages used with the M9000 310 and M9000 320 Weather Shield Enclosures M9106 xGx 2 Series Electric Non Spring Return Actuators Installatio...

Page 2: ...Appliance Cord 6 Conductor 18 AWG Wire Gauge 43 in 109 cm 1 Shaft Extender with Set Screw M9000 320 Kit Only 1 It is recommended that 1 2 in liquid tight conduit and 1 2 in National Pipe Thread NPT li...

Page 3: ...ble 2 Weather Shield Enclosure Dimensions in mm Dimension Weather Shield Enclosure M9000 310 M9000 320 A 7 7 8 200 13 3 8 340 B 4 23 32 120 5 29 32 150 C 3 17 32 90 4 23 32 120 D 4 27 32 123 6 1 32 15...

Page 4: ...ted from the inside of the enclosure so that the nitrile patch seals the mounting hole in the base 6 Install the enclosure and mounting bracket assembly onto the damper shaft extension Orient the asse...

Page 5: ...re base using two M3 x 8 mm Phillips screws and M4 washers included with the kit Tighten the Phillips screws to a torque of 15 to 20 lb in 1 7 to 2 3 N m 4 Orient the two mounting brackets onto the pr...

Page 6: ...from Step 3 14 Center the shaft or shaft extension in the actuator hub For the M9220 reinstall the actuator gripper assembly and secure in place using the spring clip Secure the actuator coupler asse...

Page 7: ...116 M9124 and M9132 4 to 122 F 20 to 50 C M9220 40 to 131 F 40 to 55 C Weather Shield Enclosure Ambient Storage Temperature Limits 40 to 176 F 40 to 80 C Electrical Connections Strain Relief Conduit F...

Reviews: