background image

M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions

6

8.

Install the two conduit fittings included with the kit 
into the enclosure base and secure them in place 
using the threaded hex nuts.

Steps 9 and 11 apply only to the M9000-320 kit when 
used with the M9220 Series actuators. For the M9000-
310 kit, proceed to Step 12.

9.

For the M9000-320 kit used with the M9220 Series 
actuators, install the shaft extension onto the input 
shaft of the valve linkage. Ensure that the set 
screws located on the shaft extension are oriented 
perpendicular to the flat surfaces on the input shaft. 
(See Figure 6.) To reduce friction, ensure that the 
shaft extension and the seal assembly are not in 
contact. A gap of no more than 1/8 in. is 
recommended between these two components.

10. Secure the shaft extension to the input shaft of the 

valve linkage using the supplied set screws and 5/
16 in. (8 mm) wrench. The recommended torque 
applied to the set screws is 100 in·lb (11 N·m). 
Tighten the screws evenly.

11. Using a flat blade screwdriver, remove and save 

the spring clip from the M9220 actuator hub and 
gripper assembly. Remove the actuator gripper 
assembly from the actuator and retain.

12. Insert the appliance cord(s) for the actuator 

through the conduit fittings.

13. Install the actuator into the enclosure/linkage 

assembly. Insert the actuator anti-rotation slots 
over the anti-rotation tab of the bracket from 
Step 3.

14. Center the shaft or shaft extension in the actuator 

hub. For the M9220, reinstall the actuator gripper 
assembly and secure in place using the spring clip. 
Secure the actuator coupler assembly to the shaft 
following the actuator mounting instructions.

Note:

Refer to the documentation included with the 

electric actuator and valve linkage for complete 
installation instructions.

15. Tighten the conduit fitting to a torque of 10 to 

15 lb·in (1.1 to 1.7 N·m) to secure the appliance 
cord in place.

16. Reinstall the cover and gasket assembly and 

secure it in place using the four cover screws 
included with the kit. Tighten the cover screws to a 
torque of 5 lb·in (0.6 N·m) maximum.

17. If the valve application is a tandem configuration, 

repeat Steps 11 through 16 on the secondary side 
of the M9000-53x Series Valve Linkage.

18. If one of the conduit fittings remains unused, seal 

the fitting using the cap plug included with the 
enclosure kit.

Repair Information

If the M9000-310 or M9000-320 Series Weather Shield 
Enclosure fails to operate within its specifications, 
replace the unit. For a replacement weather shield, 
contact the nearest Johnson Controls representative.

IMPORTANT:

The conduit fittings must be installed 

properly to ensure a tight seal. Water or moisture 
may damage or affect the operation of the electric 
actuator within the enclosure.

Figure 6: Proper Mounting Position for Shaft 

Extension

F

IG

:m

n

tg

_

p

o

s

IMPORTANT:

The cover and gasket assembly 

must be installed properly to ensure a tight seal. 
Water or moisture may damage or affect the 
operation of the electric actuator within the 
enclosure.

Summary of Contents for M9000-320 Series

Page 1: ...nformation on the M9000 Series Electric Actuators and Valve Linkages used with the M9000 310 and M9000 320 Weather Shield Enclosures M9106 xGx 2 Series Electric Non Spring Return Actuators Installatio...

Page 2: ...Appliance Cord 6 Conductor 18 AWG Wire Gauge 43 in 109 cm 1 Shaft Extender with Set Screw M9000 320 Kit Only 1 It is recommended that 1 2 in liquid tight conduit and 1 2 in National Pipe Thread NPT li...

Page 3: ...ble 2 Weather Shield Enclosure Dimensions in mm Dimension Weather Shield Enclosure M9000 310 M9000 320 A 7 7 8 200 13 3 8 340 B 4 23 32 120 5 29 32 150 C 3 17 32 90 4 23 32 120 D 4 27 32 123 6 1 32 15...

Page 4: ...ted from the inside of the enclosure so that the nitrile patch seals the mounting hole in the base 6 Install the enclosure and mounting bracket assembly onto the damper shaft extension Orient the asse...

Page 5: ...re base using two M3 x 8 mm Phillips screws and M4 washers included with the kit Tighten the Phillips screws to a torque of 15 to 20 lb in 1 7 to 2 3 N m 4 Orient the two mounting brackets onto the pr...

Page 6: ...from Step 3 14 Center the shaft or shaft extension in the actuator hub For the M9220 reinstall the actuator gripper assembly and secure in place using the spring clip Secure the actuator coupler asse...

Page 7: ...116 M9124 and M9132 4 to 122 F 20 to 50 C M9220 40 to 131 F 40 to 55 C Weather Shield Enclosure Ambient Storage Temperature Limits 40 to 176 F 40 to 80 C Electrical Connections Strain Relief Conduit F...