10
Network Communications—N2 Communications Bus
This section describes briefly what you need to know when planning to
install the N2 Bus.
The N2 Bus requires no additional space than is provided within the NCU
and NEU enclosures.
The N2 Bus repeater should be installed in an inconspicuous location
accessible to building maintenance personnel. To meet NEC requirements,
the repeater must be installed in an enclosure, and the line (120 VAC) and
low voltage (N2 Bus) must be separated by two inches. The recommended
enclosure is the BZ-1000-7. Another option is to use the AS-ENC100-0
enclosure with the repeater’s cover removed. The 2121 power supply is a
calculator-type supply. See Table 1 for dimensions of these devices.
If you are using optical fiber, consider the minimum bend radius of the fiber
cable you are using. While handling the cable,
do not
bend it at right angles.
A minimum radius of cable must be maintained. (Refer to the fiber cable
manufacturer’s guidelines for the bend specification.) Adhering to the
bending rules may dictate where you can locate the units and how large an
enclosure must be used to install the units and still adhere to the rules.
Table 1: Device Dimensions
Device
Dimensions
N2 Bus Repeater
177.8 H x 109.2 W x 53.3 D mm (7.0 x 4.30 x 2.10 in.)
BZ-1000-7 Enclosure
259 H x 249 W x 76 D mm (10.2 x 9.8 x 3.0 in.)
AS-ENC100-0 Enclosure
173 H x 185 W x 119 D mm (6.8 x 7.3 x 4.7 in.)
2110 Fiber Optic Modem
76 H x 44.5 W x 16 D mm (3.0 x 1.75 x 0.625 in.)
2121 Power Supply
38 H x 51 W mm (1.5 x 2.0 in.)
The operating environment for the N2 Bus and its components must
maintain temperatures within the range of 0 to 50°C (32 to 122°F) while
maintaining relative humidity at a value of 10 to 90% (non-condensing).
The operating environment for the repeater must maintain temperatures
within the range of 0 to 70°C (32 to 158°F) while maintaining relative
humidity at a value of 0 to 95% (non-condensing).
If the N2 Bus is installed in an area of the country that often experiences
thunderstorms and the N2 Bus is wired between the buildings, surge
protection or optical fiber for the bus is recommended. Refer to
Installing
the Surge Protector
in the
Installation Procedures
section of this
document.
The repeater requires an external source of 115 VAC at 0.05A
(or 230 VAC at 0.03A) at a frequency of 60 Hz (or 50 Hz). The
recommended power supply for the 2110 fiber modem is the
S.I. Tech 2121. It converts either 110/220 VAC 60/50 Hz to 12 VDC
(8 watts). The power supply requires an electric wall outlet nearby.
Planning
Considerations
Space
Environment
Power