Network Communications—N2 Communications Bus
9
Fiber Optic Modems (S.I. Tech 2110)
--These are communication
devices that provide conversion between standard N2 signals (RS-485)
and fiber optic signals. Note that one pair of modems is needed for each
conversion between the standard N2 cable and fiber cable.
Note: We recommend that you use only the S.I. Tech 2110 fiber modems
on the N2 Bus. These modems were tested as fully functional with
the Metasys
system and found to be transparent to Metasys
system operation and functions. Other modems are available, but
because design changes were made to the 2110 to make it
compatible with the Metasys Network, other modems may not
work.
Power Supply (S.I. Tech 2121)
--Resembling a calculator power
supply, this component provides power to the 2110 optic converter.
Each 2110 modem requires one 2121 Power Supply.
9-Pin Connector Kit (Male)
--This kit is required to construct a 9-pin
connector and hood for terminating the N2 Bus cable to the 9-pin female
connector on the 2110 fiber modems. (The modems do not have a 3-point
terminal block for the N2 as do other N2 devices.) The connector kit needs
to use D-style connectors (solder style).
Cable
--The N2 Bus can use either a solid or stranded type of the
following wires: 3-wire twisted cable; two twisted pair telephone cable;
and two twisted pairs with a shield. Duplex optical fiber can also be used.
Surge Protector (TE/JC04C12)
--The surge protector guards the
N2 Bus from most induced voltage transients resulting from natural or
man-made disturbances. It is recommended if the N2 Bus is to be wired
between buildings.
In addition to these components, internal N2 Bus circuitry is included on
the boards of all N2 devices and on the NCU and NEU base frames.
R
T
S.I. TECH
MINI OPTICAL BIT-DRIVER
MODEL 2110