D-308439 MP-802 PG+ Rev.0
Local diagnostics test
After power-up or closing the cover, the device automatically enters Test Mode for 15 minutes. To
manually enter the devices into Test Mode refer to the Control Panel Installer Guide.
1.
Before you start the test, remove the device cover from the base. See Figure 3.
2.
Close the cover to return the tamper switch to its normal position.
3.
The device enters a 2 minute stability period. During this time the red LED blinks.
4.
Walk-test the coverage area. See the figure below. Walk across the far end of the coverage
pattern in both directions. The red LED lights each time your motion is detected followed by 3
LED blinks.
The following table indicates received signal strength indication:
Table 3: Signal strength indication
LED response
Reception
Green LED blinks
Strong
Orange LED blinks
Good
Red LED blinks
Poor
No blinks
No communication
Important:
Reliable reception must be assured. Therefore, poor signal strength is not
acceptable. If you receive a poor signal from the device, relocate it and re-test until a
strong signal strength is received.
Note:
It is recommended to have a strong signal strength and you must verify the
signal strength using the control panel's diagnostic test. For detailed Diagnostics Test
instructions, refer to the control panel installer guide.
MP-802 PG+ Wireless PIR Motion Detector Installation Guide
15