OPTIONAL EQUIPMENT

MPM-2:  

Main Power Meter for MPS-24A. Includes battery

voltage and charging current meters, mounting hardware,

and cable.

JCI-LBB(R) BATTERY BACKBOX

Dimensions:  

Box: 24.0" (61.0 cm) wide x  14.0" (35.6 cm)

high x 7.75" (19.7 cm) deep. Door: 24.125" (61.3 cm) wide

x 14.25" (36.2 cm) high x (door adds 0.063" [approx. 0.16

cm] to depth).

Four-Wire Smoke Detector/Annunciator Power

24 VDC (20.4-26.4, 200 mV ripple), 1 amp max.  Filtered, regulated 

and resettable. Power-limited but must be  supervised via a UL 

approved Power Supervision Relay.

Notification Appliance/Annunciator Power

Power-limited, filtered, regulated, non-resettable, 

3 amps (in alarm) max. JP5 may be cut to 

convert this notification appliance power (TB3 

terminals 3 and 4) to a resettable, 2 A maximum 

circuit. This output can also be used to power 

ACS series annunciators (do not cut JP5). 

Secondary Power

27.6 VDC, supervised and power-limited.

Fast charge = 2 amps, trickle charge = 20 mA.

Earth Ground

Connect to chassis via a

Grounding Cable Assembly.

Ground Fault
Battery Fail
AC Power Fail
High Charge LED

JP5: 

Cut to make 

notification appliance power 

on TB3 terminals 3 and 4 a 

resettable, 

2-amp maximum circuit.

JP2: 

must be cut otherwise 

a short on the notification 

appliance power circuit 

(terminals 3 and 4) would 

register incorrectly as loss of 

primary (AC) power. (IFC-

2020/-1010 only)

MPM-2 Voltmeter/Ammeter Connector

Neutral In

Neutral Out

Hot In

Hot Out

B

Battery -

-

+

-

+

Cut R27 to disable 

Earth Fault Detection.

Primary Power

120 VAC, 50/60 Hz, 1.8 A max.

0713mpm2.wmf

6040bb55.wmf

Earth Ground

Connect to chassis via a

Grounding Cable Assembly.

+