FCU Controller Installation
Guide
17
INPUT 3 (I3) - SPACE/RETURN AIR TEMPERATURE
WIRING
Input 3 must be wired to the Return Air Temperature if a JCI thermostat
(Intelligent or TSO STAT) is used. If a JCI sensor (Room or Room Override
Sensor) is used, Input 3 must be wired to Space Temperature. Wiring for I3 is
shown in Figure 10. To wire I3 to a thermistor:
1
. Select the correct jumper setting for a thermistor on
J7
.
2
. Connect one lead of the thermistor to input terminal
I3
on terminal
block
J2
.
3
. Connect the other lead to one of the
GND
terminals.
NOTE:
Only a 10K Type II (CP Curve) thermistor may be used.
J4
J5
J6
J7
J8
J9
J2
THERMISTOR
J9
J7
GN I5
I4 GN I3 I2
VOU
I1
GN
I6
Figure 10. I3 - Thermistor Wiring.