Installation Guide
FCU Controller
18
INPUT 4 (I4) - OUTSIDE AIR /SUPPLY WATER TEMPERA-
TURE WIRING
Input 4 must be wired to the Outside Air Temperature or the Supply Water
Temperature. Wiring for I4 is shown in Figure 11. To wire I4 to a thermistor:
1
. Select the correct jumper setting for a thermistor on
J6
.
2
. Connect one lead of the thermistor to input terminal
I4
on terminal
block
J2
.
3
. Connect the other lead to one of the
GND
terminals.
NOTE:
Only a 10K Type II (CP Curve) thermistor may be used.
J9
J6
J4
J5
J6
J7
J8
J9
J2
THERMISTOR
GND I5
I4 GND I3 I2
VOUT
I1
GND
I6
Figure 11. I4 - Thermistor Wiring.