background image

 
 

Installation Sheets Manual 

121 

 

Temperature Controls Section 

 

 

Technical Bulletin 

A70, A72 

 

 

Issue Date 

0119 

©  2019 Johnson Controls 

1

 

  Code No. LIT-121121 
  Part No. 997-202, Rev. F 

A70, A72 Series Temperature Controls A70 Single-Pole and 

Four-Wire Two-Circuit A72 Two-Pole Construction 

 

Application 

The A70 single-pole and A72 
two-pole controls incorporate a 
load-carrying, contact structure 
which provides direct control of 
AC motors within the control 
rating.  (See cover label for 
electrical rating.) 

All Series A70, A72 controls are 
designed for use 

only

 as 

operating controls.  Where an 
operating control failure would 
result in personal injury and/or 
loss of property, it is the 
responsibility of the installer to 
add devices (safety, limit 
controls) or systems (alarm, 
supervisory systems) that 
protect against, or warn of, 
control failure. 

Operation 

Controls are available with either 
CLOSE high -- OPEN low or 
OPEN high -- CLOSE low 
contact action for heating or 
refrigeration applications.  The 
snap-acting contacts are 
operated by a temperature 
sensing element.  On the 
A70 controls with auxiliary 

contact, the auxiliary contact 
closes to actuate a signal or 
other auxiliary circuit at the 
same time the main contact 
opens.  (See Fig. 6.) 

Installation 

Mounting 

The A70 control in the NEMA 1 
enclosure must be located in 
areas protected from the direct 
effects of weather.  If the control 
is directly exposed to the 
weather or other wet 
environments, it must be 
equipped with an outdoor 
enclosure.  Mount the control on 
a flat surface or panel board by 
two screws or bolts through the 
holes in the back of the case.  
Controls are supplied without 
brackets unless specified.  The 
standard bracket is Part Number 
271-350.  The desired mounting 
position is with the element 
bellows pointing down. 

General Instructions 

1.  Avoid sharp bends or kinks 

in the capillary tubing. 

 

2.  Style 1 (for clamp contact or 

liquid immersion) -- be sure 
the bulb is securely 
clamped to the evaporator 
coil, or is completely 
immersed in the liquid. 

3.  Style 18 for air temperature 

control -- locate the bulb 
where there is free air 
circulation.  Make sure the 
bulb does not contact a wall 
surface. 

4.  Make sure the equipment's 

electrical load is not in 
excess of the control's 
electrical rating. 

5.  Coil and secure the excess 

capillary length to avoid 
vibration.  Allow some slack 
in the capillary to avoid 
“violin string” vibration which 
can cause the tubing to 
break.  Do not allow the 
tubing to rub against metal 
surfaces where friction can 
damage the capillary. 

6.  Do not use the control on 

applications where 
temperature exceeds the 
maximum allowable 
temperature.  See the 
Maximum Bulb Temperature 
table. 

 

Fig. 1 -- A70 Temperature 

Control with a style 1 sensing 

element.

 

 

 

Summary of Contents for PENN A70 Series

Page 1: ...ntrol in the NEMA 1 enclosure must be located in areas protected from the direct effects of weather If the control is directly exposed to the weather or other wet environments it must be equipped with an outdoor enclosure Mount the control on a flat surface or panel board by two screws or bolts through the holes in the back of the case Controls are supplied without brackets unless specified The st...

Page 2: ...acts are LINE M1 The action of the main contacts are shown on the cover label Figure 6 shows a typical wiring hookup Where it is desirable for the user to increase or decrease the DIFFERENTIAL ONLY external adjusting knob is supplied on differential screw as shown in Fig 4 Knob is provided with stops and factory assembled to permit change only within a specified range External adjusting knob may b...

Page 3: ...3 Checkout Procedure The operating point of the control should be confirmed by an accurate thermometer Before leaving the installation observe at least three complete operating cycles to be sure that all components are functioning correctly If the control setting is outside the normal operating range of the controlled device the operation of the control should be simulated by actuating the contact...

Page 4: ...Johnson Controls and PENN are registered trademarks of Johnson Controls in the United States of America and or other countries All other trademarks used herein are the property of their respective owners Copyright 2019 by Johnson Controls All rights reserved ...

Reviews: