Operating manual- SAB 355 (including ATEX)
54/63
004059 en 2019.11
EU
designation
Reference
model
RWF II
Compressor
model
Discharge flange to
separator flange
Suction flange
Bolt size
Torque
(ft-lb)
Bolt size
Torque
(ft-lb)
SAB 355 S
496
SGC 3511
M24 x 3.0
240
M30 x 3.5
350
SAB 355 L
676
SGC 3515
M24 x 3.0
240
M30 x 3.5
350
SAB 355 E
856
SGC 3519
M24 x 3.0
240
M30 x 3.5
350
SAB 355 X
1080
SGC 3524
M24 x 3.0
240
M30 x 3.5
350
Table 14: Torque requirements
Note:
* Based on:
a.
Gaskets-Garlock® Blue-Gard® 3300
b.
Bolts-class 8.8 or stronger hex head bolts, lightly oiled and clean.
8.3
Monitoring of operation
To ensure satisfactory operation, it is required that you enter certain routines in a logbook on a
regular basis. You can use the items listed in the
Start-up log
, which is page 2 of the
Checklist
il-
lustrated in Fig. 24. The service engineer will need this information in connection with, for exam-
ple, error reports.
In addition to the items listed in the start-up log, all other activities of service, maintenance or re-
pair work must be entered into your logbook as required by EN 378 and national laws.
Checklist
Along with this Operating manual we have provided a
Checklist
, as shown in Fig. 24, which will
serve as a help to the service engineer and
must be filled in during commissioning and
start-up
.
Keep the filled-in checklist, and send a copy to SABROE Factory as documentation that the unit
has been installed and commissioned correctly. The checklist will be required in case of a warranty
issue.