Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
52/168
008831 en 2020.10
4.20
Oil carry-over to plant
Total oil carry-over estimate
Formula: 0.36 x total ppm value x total mass flow (kg/s)
(COMP1) = > (kg/100 h)
The
COMP1
calculation program provides the discharge temperature and the circulated mass
flow of refrigerant through evaporator, economiser and side load. In the formula, the total mass
flow (all single flow of refrigerant to be added provides condenser mass flow or total mass flow)
must be used.
The COMP1 calculation program also provides the oil separator load (%).
Total oil carry-over calculation
Oil vapour pressure calculation based on an empiric formula with good conformity to practice
experience:
Alternatively, use steam pressure from oil company.
Dalton’s law for partial pressure of two substances in vapour form gives good conformity with
practice experience.
Liquid oil aerosol carry-over depends on oil separator, oil separator challenge flow, refrigerant, oil
type, solubility, pressures and temperatures.
10
)
273
1
220
*
1
.
1
1
(
*
)
1270
*
12
(
+
-
+
+
=
Disch
t
Fp
Fp
oil
P
Fp = Flash point (Oil data)
[°C]
t
disch
= Discharge temperature
[°C]
[torr]
00133
.
0
*
000
.
000,
,
1
*
*
*
,
Ref
Disch
oil
oil
oil
M
P
M
P
ppm
Vapour
=
[ppm]
P
oil
=
Oil vapour pressure
[torr]
P
Disch
=
Discharge pressure saturated
[bar, a]
M
oil
and M
Ref
=
Molecular weight for oil
and refrigerant
[kmol/kg]
,
1
oil
ppm
Vapour
=
1
+
Oil separator load (%)
*
Vapour, ppm
oil
(Theoretical)
100
(Theoretical)
(Practical)
R717:
Oil separator load (%) * 14
100
HC/HCFC/HFC:
Oil separator load (%) * 25
100
Total oil carry-over (ppm) = Vapour (ppm) + liquid (ppm)
(Practical)