Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
008831 en 2020.10
17/168
2.5
Labelling of explosion-proof equipment
ATEX:
The compressor area of application is indicated next to the Ex-sign on the name plate.
II 2 G T3/T4
II
Material group:
II indicates that the equipment is suitable for use in industrial areas above ground.
2
Material category:
2 indicates that the equipment is suitable for use in areas with possible occurrence of ex-
plosive gasses.
G
Hazardous environment:
G indicates that the equipment is suitable for use in potentially explosive gas, vapour
and fog atmospheres.
T3/T4
Temperature class:
indicates the surface temperatures that may occur on the compressor.
Warning!
On ATEX-executions, the limits in
must always be respected.
Temp. class
Max. surface
temp.
Max. temperature of oil to
shaft seal
Min. ignition temperature
of oil
T1
450°C
380°C
500°C
T2
300°C
230°C
350°C
T3
200°C
130°C
250°C
T4
135°C
65°C
185°C
T5
100°C
30°C
150°C
T6
85°C
15°C
135°C
Table 2: Temperature classes - screw compressors