T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
Installation Instructions
9
MenuScro
Gives the option of having the
display continuously scroll the
parameters.
Default:
on
(off):
The scroll is inactive.
(on):
The scroll is active.
Lockout
Selectable Lockout Levels for
limiting end-user keypad interaction.
Default:
0
Function
Lockout Level
(0)
(1)
(2)
Occupancy
Override
Access
Access
No Access
Permanent
Temperature
Setpoints
Access
No Access
No Access
Temporary
Temperature
Setpoints
Access
Access
No Access
Humidity
Setpoints
Access
No Access
No Access
System Mode
Setting
Access
No Access
No Access
Fan Mode Setting
Access
No Access
No Access
Schedules
Setting
2
Access
No Access
No Access
Clock Setting
2
Access
Access
Access
Permanent Hold
2
Access
No Access
No Access
Pwr del
3
Sets the delay time period at
controller powerup, or each time
power is removed and reapplied,
before any operation (fan, heating,
or cooling) is authorized. Also can
be used to sequence the startup of
multiple units in one location.
Default:
10.0 sec
Range:
10.0
to
120.0 sec
Frost pr
Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the controller.
Default:
off
(on):
Enabled
(off):
Disabled
Heat max
4
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default:
90.0°F/32.0°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Cool min
4
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default:
54.0°F/12.2°C
Range:
54.0°F/12.2°C
to
100.0°F/37.7°C
Table 2: Installer Configuration Menu (Part 2 of 6)
Parameter
Appearing
on Display
Description and Default
Selection Options