Figure 3: Terminal Block Wiring Designations (LED OFF

Mode and Manual Override PB Enabled)

.

Figure 4: Terminal Block Location and Wiring

Table 1: Terminal Block Wiring

Terminal

Signal Designation

1

Temperature Sensor and Manual Override

2

Temperature Sensor Common

3

Setpoint Common and LED Common

4

Setpoint

5

1

24 VAC (+15 VDC - VMA only)

1

6

Common (for Power, Zone Bus, or Manual

Override)

7

Zone Bus

8

LED and Manual Override

1

The +15 VDC power supply is used only when a TE-6800

Series sensor is connected to a Variable Air Volume Modular

Assembly (VMA) controller.

1

The +15 VDC power supply is used only when a TE-6800

Series sensor is connected to a Variable Air Volume Modular

Assembly (VMA) controller.

Note: 

Manual Override is selected for either

Terminals 1 and 6 to short sensor (with DIP switch

set for LED Off) or Terminal 6 and Terminal 8 to short

LED (with DIP switch set for LED On).

Modular Jack Wiring (TE-68xP Models)

The modular jack connection is shown in Figure 1. Make

modular jack electrical connections to the 8-pin RJ45

connector, using 8 conductor standard or plenum-

rated telephone cables. Terminals are identified in Table

2. Insert the modular jack connector with the proper

polarity (not reversed). Misalignment can cause damage.

Refer to the controller documentation to determine the

appropriate cable assembly.

Important: 

Do not insert a 6-pin connector or

anything other than an RJ-45 8-pin connector into the

8-pin jack on the back of the TE-6800 Temperature

Sensor to prevent damaging the modular jack.

Table 2: Modular Jack Pin Designations

Modular

Jack Pin

Number

Signal Designation

1

LED and Manual Override

2

Setpoint

3

Temperature Sensor and Manual Override

4

Temperature Sensor Common

5

1

24 VAC (+15 VDC - VMA only)

1

6

Common (for Power, Zone Bus, or Manual

Override)

7

Setpoint Common

8

Zone Bus

1

The +15 VDC power supply is used only when a TE-6800

Series sensor is connected to a VMA controller.

Setup and Adjustments

Controller Configuration Switch

A DIP switch configures the TE-6800 for use with the

desired controller by enabling or disabling the manual

override PB and the LED, in appropriate models.
To change the controller mode, use the three position

DIP switch located on the Printed Circuit Board (PCB).

See Figure 5 and consult Table 4 to determine controller

compatibility.

 NOTICE

Risk of Property Damage

Do not use switch settings other than those shown

in Figure 5. Using other switch settings may cause

incorrect controller operation or damage to the

element, controller, [and/or] controlled equipment.

TE-6800 Series Temperature Sensors Installation Guide

3

Summary of Contents for TE-6800 Series

Page 1: ...pervision ou d alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du sensor Installation Special Tools Needed A 1 16 in 1 5 mm hex wrench or a Johnson Controls T 4000 119 hex head adjustment tool is required during installation Accessories To install the TE 6800 Series Temperature Sensor on a wall...

Page 2: ...ons in accordance with local national and regional regulations Figure 1 Modular Jack Pin Number Assignments Keep wires as short as possible to minimize sensor error Each 250 ft 76 m run of 18 AWG wire or 50 ft 15 m of 24 AWG wire creates 1F 0 56C error for a nickel sensor or 1 5F 0 83C error for a platinum sensor due to wire resistance To maintain less than 1F 0 56C error for nickel or 1 5F 0 83C ...

Page 3: ...ity not reversed Misalignment can cause damage Refer to the controller documentation to determine the appropriate cable assembly Important Do not insert a 6 pin connector or anything other than an RJ 45 8 pin connector into the 8 pin jack on the back of the TE 6800 Temperature Sensor to prevent damaging the modular jack Table 2 Modular Jack Pin Designations Modular Jack Pin Number Signal Designati...

Page 4: ...ctory set up down and up The controller determines the LED mode LED Mode NO PB LED and PB Disabled but Sensor Enabled Switch positions are all down LED is off and the PB does not function Figure 5 DIP Switch Positions Table 4 Controller Compatibility with LED Mode and PB Features Recognized by Controller Types of TE 6800 LED Mode Figure 5 Features Enabled on TE 6800 AHU UNT1100 VAV1xx or UNT1xx 1 ...

Page 5: ... free from dust or obstruction If the TE 6800 temperature sensor fails to operate within its specifications replace the unit For a replacement sensor contact the nearest Johnson Controls representative Technical Specifications Table 5 TE 6800 Series Temperature Sensors technical specifications Specification Description Temperature Sensor 1000 ohm thin film nickel Temperature Coefficient Approximat...

Page 6: ...om misapplication or misuse of its products Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open source software infor...

Reviews: