background image

505309-UIM-D-0511

12

Johnson Controls Unitary Products

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.

SUPPLY VOLTAGE CONNECTIONS

1. Provide a power supply separate from all other circuits. Install over-

current protection and disconnect switch per local/national electrical
codes. The switch should be close to the unit for convenience in
servicing. With the disconnect or fused switch in the OFF position,
check all wiring against the unit wiring label. Refer to the wiring dia-
gram in this instruction.

2.

Remove the wiring box cover screws. Route all power wiring
through a conduit connector or other proper bushing that has been
installed into the unit opening and the junction box. In the junction
box there is a black wire, a white wire and a green ground screw.
Connect the power supply as shown on the unit’s wiring label
located on the inside of the blower compartment door, or the wiring
schematic in this section. Connect the black wire to L1 (hot) from
the power supply. Connect the white wire to neutral. Connect the
ground wire (installer-supplied) to the green (equipment ground)
screw. An alternate wiring method is to use a field-provided 2” (5.1
cm) x 4” (10.2 cm) box and cover on the outside of the furnace.
Route the furnace leads into the box using a protective bushing
where the wires pass through the furnace panel. After making the
wiring connections replace the wiring box cover and screws. Refer
to Figure 17.

3.

The furnace's control system requires correct polarity of the power
supply and a proper ground connection. Refer to Figure 17.

LOW VOLTAGE CONTROL WIRING CONNECTIONS

Install the field-supplied thermostat by following the instructions that
come with the thermostat. With the thermostat set in the OFF position
and the main electrical source disconnected, connect the thermostat
wiring from the wiring connections on the thermostat to the terminal
board on the ignition module, as shown in Figures 18 or 19. Electronic
thermostats may require the common wire to be connected. Apply
strain relief to thermostat wires passing through cabinet. If air condition-
ing equipment is installed, use thermostat wiring to connect the Y and C
terminals on the furnace control board to the proper wires on the con-
densing unit (unit outside). 

The 24-volt, 40 VA transformer is sized for the furnace components
only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an
air conditioning unit contactor.

Table 7: 

Ratings & Physical / Electrical Data

Input - HI/LOW 

Output - HI/LOW 

Nominal Air Flow 

Total Unit

AFUE 

Hi Fire Air Temp Rise 

Lo Fire Air Temp Rise 

MBH kW MBH kW CFM m3/min 

Amps 

%  °F 

°C  °F 

°C 

60/39 

18/11 

58/37 

17/11 

1200 

34 

10 

96 

35 - 65 

19.5 - 36 

35 - 65 

19.5 - 36 

80/52 

23/15 

77/50 

22/14 

1200 

34 

10 

96 

45 - 75 

25 - 41.6 

20 - 50 

11.1 - 27.8 

80/52 

23/15 

77/50 

22/14 

1600 

45.3 

11.5 

96 

45 - 75 

25 - 41.6 

25 - 55 

13.9 - 30.5 

100/65 

29/19 

96/62 

28/18 

1600 

45.3 

11.5 

96 

35 - 65 

19.5 - 36 

35 - 65 

19.5 - 36 

100/65 

29/19 

96/62 

28/18 

2000 

56.6 

17 

96 

45 - 75 

25 - 41.6 

20 - 50 

11.1 - 27.8 

120/78 

35/23 

115/75 

33/22 

2000 

56.6 

17 

96 

45 - 75 

25 - 41.6 

35 - 65 

19.5 - 36 

Max. Outlet Air Temp 

Blower 

Blower Size 

Max. Over Current 

Min. Wire Size 

Operating Weight 

°F 

°C 

HP 

Amps 

in. 

cm 

Protect 

(awg) @ 75ft.one way 

lbs. 

kg. 

170 

76.7 

1/2 

11 x 8 

27.9 x 20.3 

15 

14 

122 

55.3 

175 

79.4 

1/2 

11 x 8 

27.9 x 20.3 

15 

14 

126 

57.1 

175 

79.4 

3/4 

8.8 

11 x 10 

27.9 x 25.4 

15 

14 

136 

61.7 

175 

79.4 

3/4 

8.8 

11 x 10 

27.9 x 25.4 

15

14 

142 

64.4 

175 

79.4 

14.5 

11 x 11 

27.9 x 27.9 

20 

12 

145 

65.7 

180 

76.7 

14.5 

11 x 11 

27.9 x 27.9 

20 

12 

156 

70.7 

 FIGURE 17:  

Electrical Wiring

Electrical Entry

Junction
Box

L1-Hot

Neutral

Connect ground
lead to screw

BLK

WHT

The power connection leads and wiring box may be relocated to the
left side of the furnace. Remove the screws and cut wire tie holding
excess wiring. Reposition on the left side of the furnace and fasten
using holes provided.

Set the heat anticipator in the room thermostat to 0.4 amps. Setting it
lower will cause short cycles. Setting it higher will cause the room
temperature to exceed the set points.

Some electronic thermostats do not have adjustable heat anticipa-
tors. They should be set to six cycles per hour. Follow the thermostat
manufacturer's instructions.

Summary of Contents for TM9T*MP

Page 1: ...drain vertical installation 16 Typical Combustion Pipe Drain Tee 17 Upflow Configuration 18 Downflow Configuration 19 Horizontal Left Configuration 20 Horizontal Right Configuration 21 Dimensions 23 H...

Page 2: ...rise per rating plate mark ing Means for providing outdoor air required for combustion Return air temperature maintained between 55 F 13 C and 80 F 27 C The air filter must be replaced upon substanti...

Page 3: ...listed below and all authorities having jurisdiction In the United States and Canada follow all codes and standards for the following using the latest edition available STEP 1 Safety US National Fuel...

Page 4: ...n FOR FURNACES INSTALLED IN THE COMMON WEALTH OF MASSACHUSETTS ONLY For all side wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in par...

Page 5: ...is access cover shall be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to...

Page 6: ...uld always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS These upflow coils are designed for installation on top of upflow fur naces only If the coi...

Page 7: ...ace is to be installed on a flat solid surface this bottom panel will provide an adequate seal to prevent air leakage through the unused bottom opening However if the furnace is to be installed on a s...

Page 8: ...e one support at the supply end of the furnace one support located approximately in the center of the furnace near the blower shelf and the third support should be at the return end of the fur nace Ma...

Page 9: ...ombustion Air Inlet Gas Pipe Entry Electrical Entry Condensate Drain Optional Return Air Cutout Either side 29 5 For Cladded door add appoximately an additional 75 C SUPPLY END 56 56 20 B 3 23 8 56 Co...

Page 10: ...er side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace Refer to Figure 13 All filters and mounting provision must be field supplied All installa tions must have...

Page 11: ...ABLE 6 Nominal Manifold Pressure Low Fire First Stage Manifold Pressures in w c First Stage Manifold Pressures kPa Altitude feet Altitude m 0 7999 8000 8999 9000 9999 0 2437 2438 2742 2743 3048 Gas He...

Page 12: ...ard on the ignition module as shown in Figures 18 or 19 Electronic thermostats may require the common wire to be connected Apply strain relief to thermostat wires passing through cabinet If air condit...

Page 13: ...C 24 Volt Hot Cool XFMR W First Stage Heat Part Number S1 2HU16700124 1 G L 8 9 T F L 8 9 T PT 8 9 ID MODELS Part Numbers SAP Legacy 265903 031 09168 2 C 24 Volt Common R 24 Volt Hot W W1 First Stage...

Page 14: ...Common Y First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR AUX Au...

Page 15: ...typical application Figure 20 If furnace staging is desired with two furnaces on a common duct where the gas burner on the first furnace operates on W1 and the gas burner on the second furnace operate...

Page 16: ...sing right side opening when viewed from the front of the furnace For all 100 120 130K input furnaces the main drain is plumbed through the casing left side opening when viewed from the front of the f...

Page 17: ...a drain on the combustion air pipe as close to the furnace as possible as shown in Figure 23 This is true for all long horizontal venting in any furnace configuration This will prevent the condensate...

Page 18: ...ff so that no sagging loops will collect and hold condensate which will cause the furnace to not operate Shorten pressure switch hose Re route and shorten pressure switch hose Shorten rain gutter hose...

Page 19: ...ch hose to this position NOTE May require the longer hose that is provided with wider cabinets Move condensate drain hose to this position may exit either side of the cabinet Move rain gutter hose to...

Page 20: ...ose to this position NOTE May require the longer hose that is provided with wider cabinets Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this position Mov...

Page 21: ...ting provided Move condensate drain hose to this position Move rain gutter hose to this position Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this positi...

Page 22: ...BS pipe is to be used any joint where ABS pipe is joined to PVC pipe must be glued with cement that is approved for use with BOTH materials Metallic materials must not be used for venting or air intak...

Page 23: ...MBUSTION AIR VENTING FIGURE 28 Dimensions TABLE 9 Elbow Dimensions Elbow A Dimension 2 Standard 2 5 16 3 Standard 3 1 16 2 Sweep 3 1 4 3 Sweep 4 1 16 TABLE 10 Equivalent Length of Fittings Fitting Equ...

Page 24: ...quirements of the gas supplier 12 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 30 5 cm or in accordance with local i...

Page 25: ...om inside the building The vent for a single pipe system must be installed as specified in the venting section of these instructions with the vent terminating as shown in Figure 30 Each furnace must h...

Page 26: ...eric zone Refer to Figure 38 for attic and crawl space termination Only the combustion air intake may terminate in the attic The vent must terminate outside Outdoor Combustion Air Combustion Air Intak...

Page 27: ...ectangular shaped duct shall only be used when the required free area of the supply opening is 9 in2 58 06 cm2 or larger When a square or rectangular duct is used its small dimen sion shall not be les...

Page 28: ...ventilation VENT BLOWER ROTATION For ease of venting the vent blower may be rotated 90 in either direc tion For upflow installations the vent may exit through the top or either side of the cabinet For...

Page 29: ...proper input rate using natural gas with a heating value of 1030 BTU Ft3 38 4 MJ m3 If the heating value of your gas is significantly different it may be necessary to replace the orifices Verify natur...

Page 30: ...300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 232...

Page 31: ...crews on main gas valve 2 Turn gas and electrical supplies on and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator scr...

Page 32: ...t be long enough to adequately cool the furnace but not so long that cold air is blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins as sho...

Page 33: ...1232 1183 1143 1080 1003 871 798 120D20MP11 High 2341 2245 2153 2072 1977 1876 1769 1642 1506 1306 Medium High 2002 1952 1878 1823 1739 1657 1563 1458 1322 1185 Medium Low 1615 1579 1533 1473 1430 136...

Page 34: ...When the proper amount of combustion air is being provided the pressure switch will close the ignition control pro vides a 17 second ignitor warm up period the gas valve then opens the gas starts to...

Page 35: ...description of 5 Red Flashes and 11Red Flashes below If the main limit switch opens five times within a single call for heat the control will indicate 4 Red Flashes and will enter a one hour soft loc...

Page 36: ...will flash three green flashes when the memory has been cleared then will resume the normal slow green flash after a five second pause SECTION XII REPLACEMENT PARTS LIST DESCRIPTION MOTOR BLOWER COMBU...

Page 37: ...eed connections shown are typical but may vary by model and application LEGENDE DS Commutateur de porte MOT Moteur soufflerie CAP Capaciteur ROS Commutateur de roulement IDM D induct moteur FS Capteur...

Page 38: ...hange without notice Published in U S A 505309 UIM D 0511 Copyright 2011 by Johnson Controls Inc All rights reserved Supersedes 505309 UIM C 0910 Johnson Controls Unitary Products 5005 York Drive Norm...

Reviews: