Configuration Guides—XT-9100 Configuration Guide 35
RI.
HI.
Type
R/W
Tag
Description
88
58
2 Bytes
CNF
AIT1
Input Type of Analog Input 1
0 0 0 0 0 X11 X10 X9
X8 X7 X6 X5 X4 X3 X2 X1
X4 X3 X2 X1
Unit of Measure
= 0000
No Units
= 0001
Degrees Celsius or Kelvin
= 0010
Degrees Fahrenheit
= 0011
Percent
X5 = 1
Enable Square Root of Input
X6 = 1
Alarm on Unfiltered Value
X7 = 0
0-10 Volts
X7 = 1
0-2 Volts, 0-20 mA or RTD
X8 = 1
20 % Suppression
X11 X10 X9
Linearization and Sensor Type
= 000
Linear (active sensor)
= 001
Nickel 1000 (JCI)
= 010
Nickel 1000 Ext. Rng
= 011
A99 Sensor
= 100
PT1000 Sensor
89
59
Number
CNF
HR1
High Range Analog Input 1
90
5A
Number
CNF
LR1
Low Range Analog Input 1
91
5B
Number
R/W (E)
HIA1
High Alarm Limit Analog Input 1
92
5C
Number
R/W (E)
LOA1
Low Alarm Limit Analog Input
93
5D
Number
R/W (E)
ADF1
Differential on Alarm Limit [units]
94
5E
Number
CNF
FTC1
Filter Constant Analog Input 1
95
5F
2 Bytes
Spare
96
60
2 Bytes
CNF
AIT2
Input Type of Analog Input 2 (bits
as AIT1)
97
61
Number
CNF
HR2
High Range Analog Input 2
98
62
Number
CNF
LR2
Low Range Analog Input 2
99
63
Number
R/W (E)
HIA2
High Alarm Limit Analog Input 2
100
64
Number
R/W (E)
LOA2
Low Alarm Limit Analog Input 2
101
65
Number
R/W (E)
ADF2
Differential on Alarm Limit [units]
102
66
Number
CNF
FTC2
Filter Constant Analog Input 2
103
67
2 Bytes
Spare