TFP1253

Page 6 of 8

460 VAC/3 PHASE/60 HZ OR 

208 VAC/3 PHASE 60 HZ CONNECTIONS 

LANDING POINTS 

LABELED L1, L2, L3

Step 2. Power Supply

NOTICE

It is recommended that a service dis-

connect be provided adjacent to the air 

compressor.

The air compressors require a dedi-

cated power supply that is terminated 

in the power supply box on the air com-

pressor as shown in Figure 3A, 3B, or 

3C as applicable. Verify the voltage 

of the power supply available for the 

air compressor is compatible with 

the voltage requirements of the air 

compressor.

NOTICE

With the TNGC-1500/2000 and the 

TNGC-3000, verify that the compres-

sor and motor starter are configured 

for operating at 208 VAC/3 phase 

when providing 208 VAC/3 phase to 

the control box.

Step 3: Plumb the Air Supply Line

For compressors in the Americas, the 

air discharge plumbing from the air 

compressor is to be connected to the 

inlet of the nitrogen generator using 

1/2 in. black steel, galvanized steel or 

copper lines. For compressors in EMEA 

and APAC, the air discharge plumb-

ing should first be connected to the 

WSD-25 water separator which then is 

to be connected to the inlet of the nitro-

gen generator.

Step 4: Plumb the Condensate 

Drain Line

The TYCO oil-less air compressor will 

discharge condensate water from the 

air receiver tank. It is recommended 

that the 1/4 in. drain connection be 

plumbed to a floor drain or building 

exterior. When plumbing to a drain is 

not feasible an evaporative collection 

chamber can be used.

Note:

 Ensure that the receiver tank auto-

drain is connected to an un-switched power 

source: 120 VAC for Americas, 230 VAC for 

EMEA and APAC.

Note:

 The Low Oil Level Sensor on the air 

compressor automatically shuts down air 

compressor until the proper oil level has 

been restored.

Care and 

Maintenance

Nitrogen Generators

The TYCO NG-1 1150, NG-1 1500, NG-1 

2000, and NG-1 3000 Stand-Alone 

Nitrogen Generators, the TNGC-1150 

Air Compressor, and TNGC-1500/2000 

and 3000 Air Compressors must be 

maintained and serviced in accordance 

with this section.

Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down 

the affected fire protection systems 

must first be obtained from the proper 

authorities. All personnel who may 

be affected by this decision must be 

notified.

Inspection, testing, and maintenance 

must be performed in accordance 

with the requirements of the NFPA, and 

any impairment must be immediately 

corrected.
The owner is responsible for the inspec-

tion, testing, and maintenance of their 

fire protection system and devices in 

460 VAC/THREE PHASE/60 HZ OR

208 VAC/THREE PHASE/60 HZ 

CONNECTIONS

LABELED L1, L2, L3

FIGURE 3A 

MODEL TNGC-1150 AIR COMPRESSOR 

AMERICAS POWER SUPPLY CONNECTIONS

FIGURE 3B 

MODEL TNGC-1500/2000/3000 AIR COMPRESSOR 

AMERICAS POWER SUPPLY CONNECTIONS

Summary of Contents for tyco NG-1 1150

Page 1: ...on on TYCO Dry Air Vent TAV D and to TFP1263 for more information on TYCO SMART Air Vent TSV D System Assembly The TYCO Nitrogen Generator unit includes the following components Steel enclosure cabinet with mem brane type nitrogen generator no nitrogen gas storage and manual bypass Power supply 120 VAC Single phase 60Hz 230 VAC Single phase 50Hz Single point nitrogen air discharge 1 2 in NPT Hour ...

Page 2: ...4605 1150 4353 2300 8706 NG 1 1500 24 3 688 11000 41640 1440 5451 2880 10902 NG 1 2000 24 688 18500 70030 2025 7666 4050 15331 NG 1 3000 35 992 22500 85172 2900 10978 5800 21955 Notes a Capacity based on NFPA 13 30 minute fill requirement of largest single system Model Number Cabinet Without Bypass Cabinet With Bypass Weight Lbs kg Width Inches mm Height Inches mm Depth Inches mm Width Inches mm H...

Page 3: ... N2 Purity at Discharge 98 or greater maximum of 2 0 oxygen N2 Pressure at Discharge Minimum of 15 psig 1 bar Max of feed air pressure minus 15 psig 1 bar N2 Water Dew Point Typically less than 70 F 57 C Note When connecting a TYCO Stand Alone Nitrogen Generator to an existing dry pipe preaction fire sprinkler system the existing fire sprinkler system s must be limited to a maximum leak rate of le...

Page 4: ... The nitrogen air discharge plumb ing from the nitrogen generator is to be connected directly to the sprinkler system valve trim using a minimum of 1 2 in to 1 in black steel galva nized steel or copper piping The size of the nitrogen air supply line is to be based on the length of pipe between the nitrogen generator and the fire sprinkler systems along with the total volume of the fire sprinkler ...

Page 5: ...GENERATOR RUNNING OUTPUT BYPASS MODE ALARM OUTPUT LEAK MONITORING OUTPUT POWER ON OFF OUTPUT NITROGEN SUPPLY LINE PRESSURE OUTPUT L1 N G PRESSURE SWITCH INCOMING POWER FUSE BOX BUILDING MANAGEMENT SYSTEM MONITORING POINTS POWER SUPPLY POWER DISTRIBUTION L1 G N N N G FIGURE 2A MODEL NG 1 1150 NG 1 1500 NG 1 2000 AND NG 1 3000 STAND ALONE NITROGEN GENERATOR AMERICAS SYSTEM SIGNAL MONITOR AND POWER S...

Page 6: ... drain connection be plumbed to a floor drain or building exterior When plumbing to a drain is not feasible an evaporative collection chamber can be used Note Ensure that the receiver tank auto drain is connected to an un switched power source 120 VAC for Americas 230 VAC for EMEA and APAC Note The Low Oil Level Sensor on the air compressor automatically shuts down air compressor until the proper ...

Page 7: ...rnal inlet piping by slowly opening the Depressurization Ball Valve in the cabinet to the left of the filter housing Step 4 Remove the filter housing by pulling down on the blue housing lock and turning the filter housing count er clock wise Step 5 Once the filter housing has been removed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartrid...

Page 8: ...he Bypass Ball Valve Step 13 Open the Inlet and Outlet Ball Valves Compressors Maintenance of the Compressor For compressor maintenance please refer to the manufacturer s recom mended maintenance plan in the owner s manual for the compressor Limited Warranty For warranty terms and conditions visit www tyco fire com Ordering Procedure TYCO will supply a list of required part numbers to order throug...

Reviews: