TFP130

Page 5 of 6

Care and  

Maintenance

The TYCO Series TY-FRL Sprinklers 

must be maintained and serviced in 

accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection system must be 

obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
Absence of an escutcheon, which is 

used to cover a clearance hole, may 

delay the time to sprinkler operation in 

a fire situation.

Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be 

painted, plated, coated or otherwise 

altered after leaving the factory. Modi-

fied or over-heated sprinklers must be 

replaced.
Care must be exercised to avoid 

damage to the sprinklers -before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Asso-

ciation (e.g., NFPA 25), in addition to 

the standards of any other authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

with any questions.
It is recommended that automatic 

sprinkler systems be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

CLOSURE

MOUNTING

SURFACE

FACE OF

SPRINKLER

FITTING

1/2±1/8"

(12,7±3,2 mm)

1/4" (6,4 mm)

TY-FRL

2-1/4" DIA.

(57,2 mm)

1-1/2" (38,1 mm)

1-3/4" (44,5 mm)

MOUNTING

PLATE

1/8"

(3,2 mm)

2-7/8" DIA.

(73,0 mm)

1/2" (12,7 mm)

CLOSURE

MOUNTING

SURFACE

FACE OF

SPRINKLER

FITTING

1/2±1/8"

(12,7±3,2 mm)

1/4" (6,4 mm)

TY-FRL

2-1/4" DIA.

(57,2 mm)

1-1/2" (38,1 mm)

1-3/4" (44,5 mm)

MOUNTING

PLATE

1/8"

(3,2 mm)

2-7/8" DIA.

(73,0 mm)

1/2" (12,7 mm)

WRENCH

RECESS

PUSH WRENCH UP TO

ENSURE ENGAGEMENT

WITH SPRINKLER

WRENCHING AREA

WRENCH

RECESS

FIGURE 4 

SERIES TY-FRL (TY1221) RECESSED PENDENT SPRINKLER 

ASSEMBLY WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT 

STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT

FIGURE 5 

SERIES TY-FRL (TY3221) RECESSED PENDENT SPRINKLER 

ASSEMBLY WITH TW0-PIECE 1/2 INCH TOTAL ADJUSTMENT 

STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT

FIGURE 6 

W-TYPE 9 SPRINKLER 

WRENCH

FIGURE 7 

W-TYPE 12 RECESSED 

SPRINKLER WRENCH

Summary of Contents for tyco TY-FRL Series

Page 1: ...K 1 2 in NPT TY1221 Pendent 2 8K 1 2 in NPT TY3121 Upright 5 6K 1 2 in NPT TY3221 Pendent 5 6K 1 2 in NPT TY4121 Upright 8 0K 3 4 in NPT TY4221 Pendent 8 0K 3 4 in NPT TY1121 is a redesignation for S1879 and G8973 TY1221 is a redesignation for S1880 and G8971 TY3121 is a redesignation for S1864 and G8974 TY3221 is a redesignation for S1865 and G8972 TY4121 is a redesignation for S1866 and G8174 TY...

Page 2: ...GHT PENDENT CROSS SECTION RECESSED PENDENT 7 16 11 1 mm NOMINAL MAKE IN WRENCH FLANGES ESCUTCHEON PLATE SEATING SURFACE WRENCH AREA STYLE 20 RECESSED ESCUTCHEON Pipe thread connections per ISO 7 1 can be provided on special request Temperature rating is indicated on Deflector DEFLECTOR 2 7 8 73 0 mm DIA 5 6 9 3 2 4 7 8 1 1 2 Deflector Strut Frame Link Assembly Seal 9 Bushing Button 7 1 2 NPT 3 5 H...

Page 3: ...leak tight 1 2 in NPT sprinkler joint should be obtained with a torque of 7 to 14 lb ft 9 5 to 19 0 N m A leak tight 3 4 in NPT sprinkler joint should be obtained with a torque of 10 to 20 lb ft 13 4 to 26 8 N m Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler Do not attempt to make up for insuf ficient adjustment in the escutcheon plate by u...

Page 4: ...SH K TYPE TEMP RATING FRAME COLOR CODE NATURAL BRASS CHROME PLATED 2 8 1 2 in NPT PENDENT TY1221 165 F 74 C Unpainted 1 2 5 212 F 100 C White UPRIGHT TY1121 165 F 74 C Unpainted 212 F 100 C White RECESSED PENDENT TY1221 w Style 20 165 F 74 C Unpainted 212 F 100 C White 5 6 1 2 in NPT PENDENT TY3221 165 F 74 C Unpainted 1 2 3 4 5 212 F 100 C White 1 2 3 5 UPRIGHT TY3121 165 F 74 C Unpainted 1 2 3 4...

Page 5: ...ce with this document as well as with the applicable standards of the National Fire Protection Asso ciation e g NFPA 25 in addition to the standards of any other authorities having jurisdiction Contact the install ing contractor or product manufacturer with any questions It is recommended that automatic sprinkler systems be inspected tested and maintained by a qualified Inspec tion Service in acco...

Page 6: ... Thread Connections Specify Series TY FRL specify SIN specify K factor specify Upright Pendent or Recessed Pendent Sprin kler Quick Response specify temper ature rating specify type of finish P N specify from Table B Recessed Escutcheon Specify Style 20 Recessed Escutch eon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 9 Sprinkler Wrench P N 5...