Model WS Specific Application Window Sprinklers 

Horizontal and Pendent Vertical Sidewall 

5.6 K-factor

Page 1 of 8 

AUGUST 2018 

TFP620

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Model WS Specific Appli-

cation Window Sprinklers are fast 

response, glass bulb-type spray sprin-

klers available in Horizontal Sidewall 

and Pendent Vertical Sidewall models.
These sprinklers are the first to be 

specifically Listed to provide com-

plete wetting and coverage for heat 

strengthened, tempered, or ceramic 

glass windows using closed sprin-

klers. As part of the testing, the gas 

flow required to achieve the time/

temperature relationship specified in 

ASTM E119 was established in a test 

furnace without sprinkler protection. A 

window assembly protected with the 

TYCO Model WS Window Sprinklers 

was then installed in the test furnace, 

and the same gas flow conditions were 

maintained for a two-hour test period. 

No cracking or visible damage to the 

window was permitted during the test 

period, even when a hose stream was 

directed at the window.
The success of the Model WS Window 

Sprinklers is based on their fast 

response thermal sensitivity and on 

their specially designed deflectors that 

ensure that the spray pattern wets the 

entire surface of the window.
Based on successful testing, the 

Model WS Window Sprinklers can be 

used as interior protection of windows 

or glazing in a sprinklered building or 

non-sprinklered building in accordance 

with Section 104 of the IBC (“Alternate 

Materials, Design and Methods of Con-

struction and Equipment”). Also, the 

Model WS Window Sprinklers can be 

used as an open sprinkler for “Outside 

Sprinkler Protection against Exposure 

Fire”, using the design requirements of 

NFPA.
As with any specific application sprin-

kler, the installation instructions 

included in this data sheet must be pre-

cisely followed. If there are additional 

local or jurisdictional installation stan-

dards/codes for window sprinklers on 

glazed window systems, this document 

does not relieve the designer/installer 

from these requirements. Consult your 

local jurisdiction to verify if or when 

these additional guidelines must be 

followed.

NOTICE

TYCO Model WS Specific Application 

Window Sprinklers described herein 

must be installed and maintained in 

compliance with this document, as 

well as with the applicable standards 

recognized by the approval agency, in 

addition to the standards of any author-

ities having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number (SIN)

TY3388 - Horizontal Sidewall 

TY3488 - Pendent Vertical Sidewall

TY3388 is a re-designation for C3388

TY3488 is a re-designation for C3488 

Summary of Contents for tyco WS

Page 1: ...nklers is based on their fast response thermal sensitivity and on their specially designed deflectors that ensure that the spray pattern wets the entire surface of the window Based on successful testing the Model WS Window Sprinklers can be used as interior protection of windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Mat...

Page 2: ...ulb allowing the sprinkler to activate and water to flow Temperature 1 5 8 DIA 41 3 mm NPT WATERWAY OF SPRINKLER CENTERLINE NOMINAL MAKE IN 7 16 11 1 mm Screw Deflector 6 THREAD 1 2 RELIEF Components Button Sealing Compression Frame Assembly 1 5 4 2 3 Bulb 54 0 mm FLATS WRENCH 2 1 8 WINDOW 20 6 mm 13 16 TOWARDS DEFLECTOR ORIENT INDICATED TOP DEFLECTOR OF SPRINKLER SPRINKLER FRAME ARMS 1 2 3 4 5 6 ...

Page 3: ...parated by a baffle or mullion of sufficient depth to act as a baffle A mullion will act as a baffle when in the case of the Pendent Vertical Side wall the mullion extends to the back of the sprinkler deflector and in the case of the Horizontal Sidewall the mullion extends to the sprinkler wrench flat Refer to Figures 3B 1 and 3B 2 Minimum Distance from Standard Sprinklers 6 ft 1 83 m unless separ...

Page 4: ...or sprinkler spacing less than 6 ft 1 83 m Maximum Pressure per Sprinkler Horizontal Sidewall 70 psi 4 83 bar The 70 psi is only for cold solder purposes If there is a baffle or a mullion of sufficient depth to act as a baffle separating the sprinklers the maximum pressure is 175 psi 12 07 bar Vertical Sidewall 175 psi 12 07 bar When acceptable to the Authority Having Jurisdiction the Model WS Spe...

Page 5: ...indow Sprinklers is 6 0 baffle by a baffle or mullion of MULLION MINIMUM SPRINKLER MODEL WS OR VERTICAL HORIZONTAL 0 4 101 6 mm MINIMUM 4 0 1 22 m MAXIMUM 8 0 2 44 m MAXIMUM when intermediate horizontal Window Sprinklers are NOT listed to protect windows mullions are present MULLION WS SPRINKLER VERTICAL MODEL INTERMEDIATE MULLION HORIZONTAL OR FIGURE 3B B 1 TO B 3 WINDOW MULLIONS AND BUTT JOINTS ...

Page 6: ...sition with the center line of the sprinkler per pendicular to the glass surface Orient the sprinkler so that the word Top indicated on the sprinkler deflector is facing the top of window frame Step 3 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 With reference to Figures 1 or 2 apply End A of W Type 20 Sprinkler Wrench only Figur...

Page 7: ...m its bulb Refer to the Instal lation section for additional information The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards recognized by the Approval agency e g NFPA 25 in addition to the stan dards of any authorities having jurisdic tion Contact the installing co...

Page 8: ...fy Model WS Specific Application Window Sprinkler TY3488 Pendent Vertical Sidewall with specify tem perature rating specify finish and P N specify 155 F 68 C Natural Brass 50 304 1 155 Signal White RAL9003 Polyester 50 304 4 155 Jet Black RAL9005 Polyester 50 304 5 155 Chrome Plated 50 304 9 155 200 F 93 C Natural Brass 50 304 1 200 Signal White RAL9003 Polyester 50 304 4 200 Jet Black RAL9005 Pol...

Reviews: