JOHNSON CONTROLS
136
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 6 - TECHNICAL DATA
NOTE:
Placement on a level surface of free of obstructions (including snow, for
winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Controls
unit controls will optimize operation without nuisance high-pressure
safety cutouts; however, the system designer must consider potential
performance degradation. Access to the unit control center assumes
the unit is no higher than on spring isolators. Recommended minimum
clearances: side to wall – 2m; rear to wall – 2m; control panel to end
wall – 1.2m; top – no obstructions whatsoever; distance between
adjacent units – 3m. No more than one adjacent wall may be higher
than the unit.
Models YCIV0287E/V
VIEW C-C
VIEW B-B
12"
CONTROL ENTRY
3" WIDE X 13 1/2" HIGH
1 1/2"
4"
POWER ENTRY
10" WIDE X 13" HIGH
1 3/4"
POWER ENTRY IS ON BOTTOM OF PANEL
88 1/8"
VIEW A-A
C
C
B
B
DIMENSIONS - 2 & 3 COMPRESSOR ENGLISH (CONT'D)
POWER ENTRY
10" WIDE X 13"
HIGH
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...