JOHNSON CONTROLS
170
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 6 - TECHNICAL DATA
ND-X NEOPRENE ISOLATOR SPECIFICATIONS
Installation of Neoprene Mounts
It is not necessary to bolt the mountings to a concrete
pad in most cases. Mountings should always be bolted
to the chiller rails. When mountings and the chiller are
installed on steel framing above the ground, the mount-
ENGLISH
SIZE
D
H
L
T
W
BC
CS
MBD
ND-C
2-9/16
2-3/4
5-1/2
1/4
2-5/16
4-1/8
1/2-13x1"
1/2"
ND-D
3-3/8
2-3/4
6-1/4
5/16
4
5
1/2-13x1"
1/2"
ND-DS
3-3/8
2-3/4
6-1/4
5/16
4
5
1/2-13x1"
1/2"
SI
ND-C
65.1
69.9
139.7
6.4
58.7
101.9
1/2-13x1"
13
ND-D
85.7
69.9
158.8
7.9
101.6
127.0
1/2-13x1"
13
ND-DS
85.7
69.9
158.8
7.9
101.6
127.0
1/2-13x1"
13
PIN 54 = N
**WEIGHT RANGE (LBS)
**WEIGHT RANGE (KG)
COLOR
YORK P/N
YORK P/N
UP TO 751 LBS
Up to 341 kg
ND-C
Yellow
029-24584-001
751-1651 LBS
341 to 749 kg
ND-D
Yellow
029-24584-002
1651-3226 LBS
749 to 1463 kg
ND-E
Yellow
029-24584-003
** Value is de-rated by 15%
Units shipped before June 15, 2008
ings should be bolted to the steel framework. Lower
the chiller on to the mountings evenly to avoid placing
excessive weight on individual isolators.
"CS" Cap Screw
BC
"MBD" Max. Bolt Dia.
Steel Plate - Top &
Bottom Neoprene
covered to prevent
corrosion
L
T
H
W
D
LD10569
Steel Plate - Top &
Bottom. Neoprene
covered to prevent
corosion.
“CS” CAP SCREW
“MBD” MAXIUM
BOLT DIAMETER
D
H
W
T
BC
L
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...