High Baseplate Temperature (Software) Fault
Each phase bank assembly contains one liquid cooled
heatsink to cool both the inverter power modules and
the converter SCR/Diode modules. Each compressor’s
inverter power module (6 IGBT’s and Gate Driver
Board) contains an internal temperature sensor (5K
ohm at 25°C) to monitor the baseplate temperature.
On two compressor chillers, the outputs from System 1
and System 2 sensors are each compared in software to
a limit of 218°F. If either sensor exceeds this limit, the
unit will fault and shut down with a controlled ramped
shutdown.
On 3 compressor chillers, the baseplate temperatures
on compressors 1 and 3 are OR’d together and the
highest of the two temperatures is compared in soft-
ware to a limit of 232°F. Compressor #2 will have its
individual power module sensor compared in software
to a limit of 232°F. If the limit is exceeded by either of
the 2 inputs, the unit will fault and shut down with a
controlled ramped shutdown.
3 compressor chillers operate at higher
baseplate temperature compared to 2 or
4 compressor chillers.
On 4 compressor chillers, the baseplate temperatures
on compressors 1 and 3 are OR’d together and the
highest of the two temperatures is compared in soft-
ware to a limit of 218°F. The baseplate temperatures on
compressors 2 and 4 are OR’d together and the highest
of the two temperatures compared in software to a limit
of 218°F. If the limit is exceeded by either of the 2 in-
puts, the unit will fault and shut down with a controlled
ramped shutdown.
This is an auto-restart safety that will lock out on the
3rd fault in 90 minutes. The fault will be a system fault
for all units. Below are the Status display fault mes-
sages for all systems.
SYS X YYYYYYYY HIGH VSD BASEPLATE TEMP
X indicates the system and YYYYYYY indicates the
system is in a “FAULT” condition and will restart when
the fault clears or “LOCKOUT” and will not restart un-
til the operator clears the fault using the keypad.
After a fault, the fan(s) and water pump will remain
energized until the inverter power module base plate
temperature(s) falls below 165°F. The system will be
allowed to restart when the inverter power module base
plate temperatures drop below this value.
It is possible for an internal sensor to fail and not sense
temperature without causing a high baseplate sensor
fault.
High VSD Internal Ambient Temperature
(Software) Fault
The VSD Logic board contains a temperature sensor,
which monitors the unit’s internal ambient tempera-
ture. If the VSD internal ambient temperature rises
above the cutout of 158°F, the unit will fault and shut
down with a controlled ramped shutdown.
This safety will not cause a lockout. The fault will be a
unit fault for all units. Following is the Status display
fault message.
UNIT YYYYYYYY
HIGH VSD INTERNAL AMBIENT TEMP
The unit will be allowed to restart when the internal
ambient temperature drops 10°F below the cutout.
YYYYYYYY indicates the unit is in a "Fault" condi-
tion and will restart when the condition clears.
Single Phase Input (Hardware) Fault
The VSD’s SCR Trigger Control board contains cir-
cuitry that checks the three phase mains for the pres-
ence of all three-line voltages. If any of the line volt-
ages are not present, the system will immediately shut
down on a fault.
This fault will not cause a lockout. The fault will be
a unit fault for 2 or 3 compressor units. Below is the
Status display fault message.
UNIT YYYYYYYY
SINGLE PHASE INPUT VOLTAGE
The fault will be a system fault 1/3 or 2/4 for 4 com-
pressor units. Two key presses of the STATUS key are
required to show the fault on both systems. Below is
the fault message for all systems.
SYS X YYYYYYYY SINGLE PHASE INPUT VOLTS
X indicates the system and YYYYYYY indicates the
system is “FAULT” and will restart when the single
phase condition clears.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...