SECTION 8 - MICROPANEL
Power Supply (Hardware) Fault
Various DC power supplies which power the VSD
Logic Board are monitored via hardware located on the
logic board. If any of these power supplies fall outside
their allowable limits, the unit will immediately shut
down on a fault.
This is an auto-restart safety that will restart after the
fault clears and lock out on the 3rd fault in 90 minutes.
The fault will be a unit fault for all units. Below is the
Status display fault message.
UNIT YYYYYYYY
VSD LOGIC BOARD POWER SUPPLY
YYYYYYY indicates the system is in a “FAULT” con-
dition and will restart when the fault clears or “LOCK-
OUT” and will not restart until the operator clears the
fault using the keypad.
Run Relay (Software) Fault
Upon receipt of either of the two types of run com-
mands (hardware and software) a 5 second timer will
commence timing. The hardware run signal comes
from the SYS X VSD Run Signal to the VSD Log-
ic Board. The software run signal comes through the
comms from the Chiller Control Board. If the missing
run signal is not asserted within the 5-second window,
the system will fault. In addition, if either run signal is
disabled while the VSD is running, the remaining run
signal must be disabled within 5 seconds after the VSD
is shut down or the system will fault. If running, the
unit will fault and shut down with a controlled ramped
shutdown.
Control Panel Info - This is an auto-restart safety that
will autostart after the 120 second anti-recycle timer
times out and will lock out on the 3rd fault in 90 min-
utes. The fault will be a system fault for 2 compressor
units. On 3 and 4 compressor units, the fault is com-
bined as a 1/3 or 2/4 system fault. Below are the fault
messages for all systems.
SYS X YYYYYYYY VSD RUN RELAY
X indicates the system and YYYYYYY indicates the
system is in a “FAULT” condition and will restart when
the fault clears or “LOCKOUT” and will not restart un-
til the operator clears the fault using the keypad.
VSD Logic Board Failure (Software) Fault
Upon receipt of the voltage and frequency commands,
the PWM generator will acknowledge receipt of the
command. If the system microprocessor does not re-
ceive the handshake within 1.5 seconds of issuing the
command, the unit will trip. This safety is only active
during precharge and during running of a compressor.
It is not active when all the compressors are shut down
and the precharge is disabled. If the VSD Logic Board
Fault occurs while the chiller is running, all systems
will immediately shut down on a fault.
This is an auto-restart safety that will auto restart after
the 120 second anti-recycle timer times out and lock
out on the 3rd fault in 90 minutes. The fault is a unit
fault for all units. Following is the fault message.
UNIT YYYYYYYY
VSD LOGIC BOARD FAILURE
VSD CT Plug (Hardware) Fault
Jumpers are installed in each CT plug on the VSD Log-
ic Board to feed back signals to indicate if the plugs
are installed or not. If either plug is not installed, a low
value is read on the digital input and the unit will im-
mediate shutdown on a fault or will not run if off.
This is an auto-restart safety that will restart after the
120 second anti-recycle timer times out and lock out on
the 3rd fault in 90 minutes. The fault is a unit fault for
all units. Following is the fault message.
UNIT YYYYYYYY
VSD CT PLUG FAULT
YYYYYYYY indicates the system is in a “FAULT”
condition and will restart or "LOCKOUT" and will not
restart until the operator clears the fault using the key-
pad.
VSD Fault Data
When a fault has occurred, the VSD Logic Board will
capture fault data. This data will be stored in the on-
board battery backed RAM for safekeeping and trans-
ferred to the panel via the communications link as soon
as possible.
A fault code will be set for the fault that initiated the
system shutdown. This fault will appear as a specific
fault in the Status message.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...