SECTION 8 - MICROPANEL
General Status Messages
UNIT STATUS
MANUAL OVERRIDE
This message indicates the chiller is operating in
MANUAL OVERRIDE mode. This message is a pri-
ority message and cannot be overridden by any other
STATUS message. When in Manual Override, no other
status message will ever be present.
UNIT STATUS
UNIT SWITCH OFF SHUTDOWN
This message indicates the UNIT SWITCH is in the off
position and not allowing the unit to run.
UNIT STATUS
DAILY SCHEDULE SHUTDOWN
This message indicates that either the daily or holiday
schedule programmed is keeping the chiller from run-
ning.
UNIT STATUS
REMOTE CONTROLLED SHUTDOWN
This message indicates that either an ISN or RCC has
turned the chiller off and is not allowing it to run.
UNIT STATUS
FLOW SWITCH SHUTDOWN
This message indicates the flow switch is not allowing
the chiller to run. There is a 1 second delay on this safe-
ty to assure the flow switch did not momentarily open.
UNIT STATUS
VSD COOLING SHUTDOWN
This message indicates the chiller is shutdown, but
running all the condenser fans, VSD glycol pump, and
VSD fan in an effort to bring the internal VSD ambient
temperature down to an acceptable level before allow-
ing the chiller to start.
SYS X REMOTE RUN CONTACT IS OPEN
This message indicates the remote start/stop contact
between 2-15 or 2-16 of the 1TB terminal block is
open. There is a 1 second delay on this safety to assure
the remote contacts did not momentarily open.
SYS X SYSTEM SWITCH IS OFF
This message indicates the system switch (software via
keypad) is turned off. The system will not be allowed
to run until the system switch is turned ON via the key-
pad.
SYS X NOT RUNNING
This message indicates the system is not running be-
cause the chilled liquid is below the setpoint or the
micro has not loaded the lead system far enough into
the loading sequence to bring the lag system on. This
message will be displayed on the lag system until the
loading sequence is ready for the lag system to start.
SYS X COOLING DEMAND SHUTDOWN
This message is only displayed in the Normal Shut-
down History display to indicate a capacity control
shutdown.
SYS X COMPRESSOR RUNNING
This message indicates the system is running as a result
of cooling demand.
SYS X SHUTTING DOWN
The compressor shutting down message indicates the
respective system is ramping down in speed prior to
shutting off. This message is displayed after the soft-
ware run signal is disabled until the VSD notifies the
Chiller Control Board the compressor is no longer run-
ning.
SYS X ANTI-RECYCLE TIMER = XXX SEC
This message indicates the amount of time left on the
respective system anti-recycle timer and the system is
unable to start until the timer times out.
SYS X DISCHARGE PRESSURE LIMITING
The Discharge Pressure Limiting message indicates
the discharge pressure load limit or discharge pressure
unloading is in effect.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...