8
SYS X SUCTION PRESSURE LIMITING
The Suction Pressure Limiting message indicates the
suction pressure load limit or suction pressure unload-
ing is in effect.
SYS X MOTOR TEMP LIMITING
The Motor Temp Limiting message indicates the motor
temp load limit or motor temp unloading is in effect.
SYS X MOTOR CURRENT LIMITING
The motor current limiting message indicates the mo-
tor current load limit or motor current unloading is in
effect.
SYS X PULLDOWN MOTOR CURRENT LIMITING
The pulldown motor current limiting message indicates
the pulldown motor current load limit or pulldown
motor current unloading is in effect based on the pro-
grammed setpoint.
SYS X ISN CURRENT LIMITING
The ISN Current Limiting message indicates the motor
current load limit or motor current unloading is in ef-
fect through the use of the YORKTalk setpoint.
SYS X REMOTE MOTOR CURRENT LIMITING
The Remote Motor Current Limiting message indicates
the motor current load limit or motor current unloading
is in effect through the use of the remote setpoint off-
set. The setpoint may be offset using a remote voltage
or a current signal. The remote current limit must be
activated for this function to operate.
SYS X VSD BASEPLATE TEMP LIMITING
The VSD Baseplate Temp Limiting message indicates
the VSD Baseplate temp is high and load limit or un-
loading is in effect.
SYS X VSD INTERNAL AMBIENT TEMP LIMITING
The VSD Internal Ambient Temp Limiting message in-
dicates the VSD internal ambient temp is high and load
limit or unloading is in effect.
SYS X SOUND LIMITING
The sound limiting message indicates the sound load
limit is in effect based on the locally programmed
sound limit from the keypad. The sound limit must be
activated for this function to operate.
SYS X ISN SOUND LIMITING
The ISN sound limiting message indicates the sound
load limit is in effect based on the ISN transmitted
sound limit setpoint. The sound limit must be activated
for this function to operate.
SYS X REMOTE SOUND LIMITING
The Remote sound limiting message indicates the
sound load limit is in effect based on the Remote con-
trolled sound limit setpoint. The setpoint may be offset
using a remote voltage or current signal. The sound
limit option must be activated for this function to oper-
ate.
Unit Safety (Fault) Status Messages
A complete listing of the unit safeties and the corre-
sponding status messages is provided on Page 245.
System Safety (Fault) Status Messages
A complete listing of the system safeties and the cor-
responding status messages is provided on Page 246.
VSD Safety (Fault) Status Messages
A complete listing of VSD safeties and the correspond-
ing status messages is provided on Page 237.
Unit Warning Messages
A complete listing of the unit warnings and the cor-
responding status messages is provided on Page 243.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...