JOHNSON CONTROLS
261
SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
8
Fault Shutdowns History
If the FAULT SHUTDOWNS History is selected, the
following screen will be displayed:
FAULT HIST XX 18-JUN-20004 10:34:58 AM
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
XX is the FAULT HISTORY shutdown number. The
display will provide the date, time, and a description of
the specific type of fault that occurred (YYY….).
The operator can view any of the stored 10 fault history
buffers. History buffer number 1 provides the most re-
cent safety shutdown information and buffer number
10 is the oldest safety shutdown information saved.
The ◄ and ► arrow keys allow scrolling between
each of the FAULT HIST buffers 1 through10. The ▲
(UP) and ▼ (DOWN) arrow keys can be used to scroll
forwards and backwards through the data in a specific
history buffer, once it is displayed.
There is a large amount of data provided under each
history. Rather than scroll sequentially through the data
in a history, which is possible using the ▼ arrow key,
the use of a combination of the ◄, ►, ▲‚ and ▼ ar
-
row keys allows fast scrolling to specific data the user
desires to view. To use this feature, the user needs to
be aware the ◄ and ► arrow keys allow scrolling to
the top of the data subgroups. Once a specific history
is selected, the history data is divided under the sub-
groups of Unit Data, VSD Data, System Data, Hours/
Starts, Setpoints, Options, and Program data. The ◄
and ► arrow keys allow moving to the first display
under the next or previous subgroup at any time. Once
the first display of a subgroup is displayed, the ▲‚ and
▼ arrow keys allow scrolling though the data in the
subgroup. The ▼ arrow key allows scrolling though
the data from first to last. When the last piece of data
is displayed, the next press of the ▼ arrow key scrolls
to the first piece of data in the next subgroup. The ▲
arrow key allows going to the previous display.
Listed below is a description of the fault data displays
and their meaning. Data will be displayed in a specific
order starting with the Status Display (System Faults
only), Fault Display, All Fault Display, Unit Data, VSD
Data, System Data, Operating Hours/Starts, Setpoints,
Options, and Program Values at the time of the fault.
Status Fault Type
SYS X COMPRESSOR RUNNING
SYS X YYYYYYYY HIGH DIFF OIL PRESSURE
This message indicates the type of system fault. This
screen is skipped if a UNIT Fault caused the shutdown.
Unit Fault Type
UNIT FAULT
LOW AMBIENT TEMP
This message indicates the type of unit fault. This
screen is skipped if a SYSTEM Fault caused the shut-
down.
All Fault Data
FAULT HIST XX ALL FAULTS ZZ OF WW
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
The ALL FAULT display indicates whether a fault oc-
curred while the unit is shutting down on another fault.
If a control panel fault occurred while the unit is shut-
ting down on a VSD fault before it is reset, the control
panel fault is an ALL FAULT of the VSD fault.
If another VSD fault occurs while the unit is shutting
down on a VSD fault, the next VSD fault will be regis-
tered as an ALL FAULT of the VSD fault.
If a VSD fault occurs during the ramp down shutdown
of a control panel fault, the VSD fault is registered as a
new fault, not an ALL FAULT
XX is the history number, YYY is the ALL FAULT
description, ZZ is the ALL FAULT number and WW
is the total number of All Faults for the current his-
tory. Sometimes, multiple faults may occur during the
shutdown and multiple displays will be observed when
scrolling through the data using the ▼ arrow. In most
cases, the ALL FAULT display will indicate NONE.
The ALL FAULT display will only indicate the cause
of the fault. No additional chiller information will be
displayed under the ALL FAULT, since a snapshot of
all chiller data was taken at the time of the first fault.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...