JOHNSON CONTROLS
70
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 6 - TECHNICAL DATA
PHYSICAL DATA (ENGLISH - HIGH EFFICIENCY)
Refrigerant R-134a
HIGH EFFICIENCY
MODEL NUMBER (YCIV____ E/V)
General Unit Data
60Hz
0157
0177
0187
0197
0207
0227
0247
Number of Independent Refrigerant Circuits
2
2
2
2
2
2
2
Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, lbs
170/170 185/170 185/185 192/192 225/192 225/225 230/230
Oil Charge, Ckt.-1/Ckt.-2, gal.
5/5
5/5
5/5
5/5
5/5
5/5
5/5
Compressors, Semihermetic Screw Qty per
Chiller
2
2
2
2
2
2
2
Condensers, High Efficiency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, ft2
235
264
293
293
323
352
352
Number of Rows
3
3
3
3
3
3
3
Fins per Inch
17
17
17
17
17
17
17
Condenser Fans
Number, Ckt.-1/Ckt.-2
4/4
5/4
5/5
5/5
6/5
6/6
6/6
Low Noise Fans
Fan Motor, HP
2
2
2
2
2
2
2
Total Chiller Airflow, cfm
104000
117000
130000
130000
143000
156000
156000
Ultra Quiet Fans
Fan Motor, HP
2
2
2
2
2
2
2
Total Chiller Airflow, cfm
104000
117000
130000
130000
143000
156000
156000
Dual Speed Fans - Normal Speed
Fan Motor, hp
2
2
2
2
2
2
2
Total Chiller, CFM
88000
99000
110000
110000
121000
132000
132000
Dual Speed Fans - Lower Speed
Fan Motor, hp
2
2
2
2
2
2
2
Total Chiller, CFM
67200
75600
84000
84000
92400
100800
100800
High Static Fans
Fan Motor, hp
5
5
5
5
5
5
5
Total Chiller, CFM
104000
117000
130000
130000
143000
156000
156000
Evaporator, Direct Expansion
Water Volume, gals.
95.0
95.0
95.0
110.0
110.0
110.0
140.0
Maximum Water Side Pressure, PSIG
150
150
150
150
150
150
150
Maximum Refrigerant Side Pressure, PSIG
235
235
235
235
235
235
235
Minimum Chilled Water Flow Rate, gpm
160
160
160
180
180
180
180
Maximum Chilled Water Flow Rate, gpm
750
750
750
750
750
750
800
Water Connections, inches
10
10
10
10
10
10
10
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...