SECTION 6 - TECHNICAL DATA
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
6
STANDARD EFFICIENCY 2-COMPRESSOR UNITS (CONT'D)
One Field Provided Power Supply Circuit. Field Connections to Factory provided
Terminal Block (Standard); or Individual System Breakers (Optional).
STANDARD EFFICIENCY YCIV_ _ _ _ S/P
STANDARD EFFICIENCY YCIV_ _ _ _ S/P
MODEL NO./NAMEPLATE
SYSTEM 1
SYSTEM 2
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED
COND. FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED
COND. FANS
YCIV S/P
INPUT
VOLTS
(9)
INPUT
FREQ
COMPRESSOR
RLA (5)
CONDENSER
FANS
COMPRESSOR CONDENSER
FANS
COMPRESSOR
RLA (5)
CONDENSER
FANS
COMPRESSOR
RLA (5)
CONDENSER
FANS
COMPRESSOR
RLA (5)
CONDENSER FANS
COMPRESSOR
RLA (5)
CONDENSER
FANS
QTY. FLA
(EA)
RLA (5)
QTY. FLA
(EA)
QTY. FLA
(EA)
QTY.
FLA
(EA)
QTY.
FLA
(EA)
QTY.
FLA
(EA)
0157
460
60
120
4
2.8
120
4
2.8
380
60
152
4
3.5
152
4
9.3
152
4
3.5
152
4
9.3
0177
460
60
159
4
2.8
105
4
2.8
380
60
201
4
3.5
201
4
9.3
133
4
3.5
133
4
9.3
0187
460
60
162
5
2.8
120
4
2.8
380
60
205
5
3.5
205
5
9.3
152
4
3.5
152
4
9.3
0207
460
60
145
5
2.8
162
4
2.8
380
60
184
5
3.5
184
5
9.3
206
4
3.5
206
4
9.3
0227
460
60
162
5
2.8
162
5
2.8
380
60
205
5
3.5
205
5
9.3
205
5
3.5
205
5
9.3
0247
460
60
193
6
2.8
160
5
2.8
380
60
245
6
3.5
245
6
9.3
203
5
3.5
203
5
9.3
0267
460
60
191
6
2.8
191
6
2.8
380
60
242
6
3.5
242
6
9.3
242
6
3.5
242
6
9.3
YCIV S/P
CONTROL
KVA (7)
UNIT SHORT CIRCUIT
WITHSTAND (KA)
FIELD WIRING & PROTECTION
FIELD WIRING & PROTECTION
STD. & ULTRA QUIET COND. FANS
HIGH HEAD/HIGH STATIC FANS
TWO-SPEED COND. FANS
TERMINAL
BLOCK
(STD)
CIRCUIT
BREAKER
(OPT)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX. IN-
VERSE TIME
CKT. BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX.
INVERSE
TIME CKT.
BRKR. RAT-
ING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER
RATING (4)
MAX.
INVERSE
TIME CKT.
BRKR. RAT-
ING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
0157
1.8
30KA
65KA
293
350
400
400
1.8
30KA
65KA
370
450
500
500
417
500
500
500
0177
1.8
30KA
65KA
326
400
450
450
1.8
30KA
65KA
413
500
600
600
459
600
600
600
0187
1.8
30KA
65KA
348
400
500
500
1.8
30KA
65KA
440
500
600
600
492
600
700
700
0207
1.8
30KA
65KA
373
450
500
500
1.8
30KA
65KA
472
600
600
600
525
600
700
700
0227
1.8
30KA
65KA
392
450
500
500
1.8
30KA
65KA
496
600
700
700
554
700
700
700
0247
1.8
30KA
65KA
433
500
600
600
1.8
30KA
65KA
547
700
700
700
610
700
800
800
0267
1.8
30KA
65KA
464
600
600
600
1.8
30KA
65KA
587
700
800
800
657
800
800
800
See page 92 for Electrical Data footnotes.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...