JOHNSON CONTROLS
89
SECTION 6 - TECHNICAL DATA
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
6
MODEL NO./NAME-
PLATE
SYSTEM 1
SYSTEM 2
SYSTEM 2
SYSTEM 3
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
YCIV
E/V
INPUT
VOLTS
(9)
INPUT
FREQ
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
0267
460
60
142
5
2.8
142
5
2.8
105
4
2.8
380
60
179
5
3.5
179
5
9.3
179
4
3.5
179
4
9.3
133
4
3.5
133
4
9.3
0287
460
60
137
5
2.8
137
5
2.8
137
5
2.8
380
60
173
5
3.5
173
5
9.3
173
5
3.5
173
5
9.3
173
4
3.5
173
4
9.3
0327
460
60
152
5
2.8
152
5
2.8
141
6
2.8
380
60
193
5
3.5
193
5
9.3
193
5
3.5
193
5
9.3
178
6
3.5
178
6
9.3
0357
460
60
181
6
2.8
181
6
2.8
139
6
2.8
380
60
229
6
3.5
229
6
9.3
229
6
3.5
229
6
9.3
176
6
3.5
176
6
9.3
HIGH EFFICIENCY 3-COMPRESSOR UNITS (CONT'D)
(One Field Provided Power Supply Circuit. Field Connections to Factory
provided Terminal Block (Standard); or Individual System Breakers (Optional).
YCIV
S/P
Control
KVA (7)
Unit Short Circuit
Withstand (KA)
Field Wiring & Protection
Field Wiring & Protection
Field Wiring Lugs
Std. & Ultra Quiet Cond. Fans
High Head/High Static Fans
High Head/High Static
Fans
Two-Speed Cond. Fans
STD Terminal
Block
OPT Circuit
Breaker
Terminal
Block
(STD)
Circuit
Breaker
(OPT)
Mini-
mum Ckt.
Ampacity
(MCA) (3)
Recommend-
ed Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Minimum
Ckt.
Ampacity
(MCA) (3)
Recommended
Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Minimum
Ckt.
Ampacity
(MCA) (3)
Recommended
Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Lugs/
Phase
(1)
Lug Wire
Range
Lugs/
Phase
(1)
Lug Wire
Range
0287
2.4
30KA
65KA
463
600
600
600
4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4
30KA
65KA
581
700
700
700
632
800
800
800
4
#2 - 600
KCM
4
#4/0 - 500
KCM
0307
2.4
30KA
65KA
486
600
600
600
4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4
30KA
65KA
610
700
700
700
659
800
800
800
4
#2 - 600
KCM
4
#4/0 - 500
KCM
0357
2.4
30KA
65KA
528
600
600
600
4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4
30KA
65KA
667
800
800
800
728
800
800
800
4
#2 - 600
KCM
4
#4/0 - 500
KCM
0397
2.4
30KA
65KA
598
700
700
700
4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4
30KA
65KA
755
800
800
800
818
1000
1000
1000
4
#2 - 600
KCM
4
#4/0 - 500
KCM
See page 92 for Electrical Data footnotes.
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...