CHILLED LIQUID AND SUCTION TEMPERATURE SENSOR INPUT VOLTAGE
TABLE 31 -
TEMPERATURE INPUT VOLTAGE SENSOR (MEASURED SIGNAL TO SHIELD AT THE SENSOR)
TEMP. (ºF)
VOLTAGE
TEMP. (ºF)
VOLTAGE
TEMP. (ºF)
VOLTAGE
16.1
1.52
35.9
2.19
55.6
2.85
16.7
1.54
36.5
2.21
56.3
2.87
17.3
1.56
37.0
2.23
56.9
2.89
17.9
1.58
37.6
2.25
57.5
2.91
18.5
1.60
38.2
2.27
58.1
2.93
19.1
1.62
38.7
2.29
58.7
2.95
19.7
1.64
39.3
2.30
59.4
2.97
20.3
1.66
39.9
2.32
60.0
2.99
20.9
1.68
40.4
2.34
60.6
3.01
21.5
1.70
41.0
2.36
61.3
3.03
22.1
1.72
41.6
2.38
61.9
3.05
22.7
1.74
42.1
2.40
62.5
3.07
23.3
1.76
42.7
2.42
63.2
3.09
23.9
1.78
43.3
2.44
63.8
3.11
24.5
1.80
43.9
2.46
64.5
3.13
25.0
1.82
44.4
2.48
65.1
3.14
25.6
1.84
45.0
2.50
65.8
3.16
26.2
1.86
45.6
2.52
66.5
3.18
26.8
1.88
46.2
2.54
67.1
3.20
27.3
1.90
46.7
2.56
67.8
3.22
27.9
1.91
47.3
2.58
68.5
3.24
28.5
1.93
47.9
2.60
69.2
3.26
29.0
1.95
48.5
2.62
69.9
3.28
29.6
1.97
49.1
2.64
70.6
3.30
30.2
1.99
49.7
2.66
71.3
3.32
30.8
2.01
50.3
2.68
72.0
3.34
31.3
2.03
50.8
2.70
72.7
3.36
31.9
2.05
51.4
2.71
73.4
3.38
32.5
2.07
52.0
2.73
74.2
3.40
33.0
2.09
52.6
2.75
74.9
3.42
33.6
2.11
53.2
2.77
34.2
2.13
53.8
2.79
34.8
2.15
54.5
2.81
35.3
2.17
55.0
2.83
Summary of Contents for YCIV0157
Page 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...