238
JOHNSON CONTROLS
FORM 201.21-NM4 (616)
238
JOHNSON CONTROLS
MICRO PANEL
System 2 - 4 Data
Data for the remaining systems 2 – 4 at the time of the
fault is displayed in the same sequence as the system
#1 data.
COMPRESSOR OPERATING HOURS AND
STARTS
HISTORY KEY (CON'T)
HOURS 1=XXXXX, 2=XXXXX, 3=XXXXX, 4=XXXXX
START 1=XXXXX, 2=XXXXX, 3=XXXXX, 4=XXXXX
This message displays compressor operating hours and
compressor starts at the time of the fault. The data and
compressor designators for compressors not present will
be blanked out.
CHILLED LIQUID SETPOINT COOLING
SETPOINTS
This message displays the programmed cooling setpoint
at the time of the fault.
SETPOINTS
LOCAL COOLING SETPOINT
= XXX.X °F
This message displays the programmed control range
at the time of the fault.
Remote Setpoint And Range
SETPOINTS
LOCAL CONTROL RANGE
= +/- X.X °F
OPTIONS
DISPLAY LANGUAGE
◄ ►
XXXXXXXXXXXXXXXXXXXX
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
GLYCOL COOLING
OPTIONS LOCAL / REMOTE CONTROL MODE
◄ ►
XXXXXXXXXXXXXXXXXXXXX
OPTIONS DISPLAY UNITS
◄ ►
XXXXXXXXXXXXXXXXXXXX
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
WATER COOLING
SETPOINTS REMOTE SETPOINT = XXX.X °F
REMOTE CONTROL RANGE = +/- X.X °F
This message displays the remote setpoint and control
range at the time of the fault.
Maximum Remote Temperature Setpoint
This message displays the maximum remote reset pro-
grammed at the time of the fault.
SETPOINTS
MAXIMUM REMOTE TEMP RESET = XXX.X °F
OPTIONS
Display Language
This message displays the language selected at the time
of the fault.
Chilled Liquid Cooling Mode
This message displays the chilled liquid temperature
mode (water or glycol) selected at the time of the
fault.
Local / Remote Control Mode
This message indicates whether Local or Remote Con-
trol Mode was selected at the time of the fault.
When Remote Control Mode is selected, control of the
Chilled Liquid Setpoint is from a remote device such
as an ISN/BAS controller.
Display Units Mode
This message indicates whether SI (°C, barg) or Imperial
units (°F, PSIG) was selected at the time of the fault.
OPTIONS LEAD / LAG CONTROL MODE
◄ ►
XXXXXXXXXXXXXXXXXXXXX
System Lead/Lag Control Mode
This message indicates the type of lead lag control se-
lected at the time of the fault. 5 choices are available:
Automatic, Sys 1 Lead, Sys 2 Lead, Sys 3 Lead, and Sys
4 Lead. The default mode will be AUTOMATIC.