42
JOHNSON CONTROLS
FORM 201.21-NM4 (616)
42
JOHNSON CONTROLS
TECHNICAL DATA
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest YORK office for application guidelines.
WATER TEMPERATURE AND FLOWS
(SI Units)
MODEL
NUMBER
YCAV
LEAVING WATER
TEMPERATURE (°C)
COOLER FLOW
(l/s)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0969
4.4
15.6
11.4
50.5
-17.7
51.7
1039
4.4
15.6
15.8
75.7
-17.7
51.7
1139
4.4
15.6
15.8
75.7
-17.7
51.7
1169
1309
4.4
15.6
18.9
75.7
-17.7
51.7
1429
4.4
15.6
18.9
78.9
-17.7
51.7
1549
4.4
15.6
22.1
78.9
-17.7
51.7
1649
4.4
15.6
22.1
78.9
-17.7
51.7
1739
4.4
15.6
25.2
88.3
-17.7
51.7
1829
4.4
15.6
25.2
88.3
-17.7
51.7
1909
4.4
15.6
25.2
88.3
-17.7
51.7