10.3 Digital Outputs
10.4 Analogue Output
1
-
36
Form 201.26.OI1(11/09)
OUTPUT
-AMB
IDENT
DESCRIPTION
IDENT
XTB7-1
1
XTB7-2
=AMB-K1
SYS 1 COMPRESSOR 1
=1-KM1
2
XTB7-3
=AMB-K2
SYS 1 LIQIUD LINE SOLENOID VALVE
=1-YLLSV
3
XTB7-4
=AMB-K3
SYS 1 COMPRESSOR 2
=1-KM2
4
XTB7-5
=AMB-K4
SYS 1 COMPRESSOR 3
=1-KM3
XTB7-6
5
XTB7-7
=AMB-K5
NOT USED
5
XTB7-8
=AMB-K6
NOT USED
6
XTB7-9
=AMB-K7
NOT USED
7
XTB7-10
=AMB-K8
NOT USED
XTB10-1
8
XTB10-2
=AMB-K17
SYS 2 COMPRESSOR 1
=2-KM1
9
XTB10-3
=AMB-K18
SYS 2 LIQUID LINE SOLENOID VALVE
=2-LLSV
10
XTB10-4
=AMB-K19
SYS 2 COMPRESSOR 2
=2-KM2
11
XTB10-5
=AMB-K20
SYS 2 COMPRESSOR 3
=2-KM3
XTB10-6
12
XTB10-7
=AMB-K21
NOT USED
13
XTB10-8
=AMB-K22
NOT USED
14
XTB10-9
=AMB-K23
NOT USED
15
XTB10-10
=AMB-K24
NOT USED
XTB8-1
16
XTB8-2
=AMB-K9
NOT USED
17
XTB8-3
=AMB-K10
SYS 1 FAULT
=1-KCR
18
XTB8-4
=AMB-K11
HYDRO KIT PUMP 2 (if fitted)
19
XTB8-5
=AMB-K12
YLAA TWO SPEED FANS SYSTEM 1 FAST/SLOW
=1-KFS
20
XTB8-6/7
=AMB-K13
EXTERNAL EVAPORATOR PUMP
or HYDRO KIT PUMP 1 (if fitted)
-XTBC2 23/34
21
XTB8-8/9
=AMB-K14
YLAA TWO SPEED FANS SYSTEM 2 FAST/SLOW
=2-KFS
22
XTB9-1/2
=AMB-K15
SYS 2 FAULT
=2-KCR
115V
115V VIA =ARD-K30
115V
115V
115V VIA =ARD-K31
OUTPUT
-AMB
DESCRIPTION
1
J15-3 (J15-7, 0V)
3-WAY VALVE OUTPUT