H compressor units (metric)
Figure 16: H compressor unit dimensions (mm)
Table 23: Additional operating height clearance
Type of chiller mounting
M (mm)
Neoprene pad isolators
44
Spring isolators 25mm deflection
25
Direct mount
19
Table 24: H9 compressor evaporator - condenser shell codes
I-K, K–K (mm)
K–O (mm)
M–M (mm)
A
2,299
2,673
2,616
B
3,150
3,242
3,315
C
641
641
724
D
508
695
584
E
4,267
4,267
4,267
Note:
1. All dimensions are approximate.
2. For compact waterboxes, see Figure 16, determine overall unit length by adding
waterbox depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 1/2 in. (13 mm) to nozzle length
for flanges connections.
4. To determine overall height, add 7/8 in. (22 mm) for isolators.
5. Use of motors with motor hoods may increase overall unit dimensions.