OUTDOOR UNITS
2-4
TC-16001-rev.5
Model: (H,Y,C)VAHP036B21S to (H,Y,C)VAHP060B21S
inch [mm]
2.4.2 Outdoor Units
•
A side view
Drain Water
Drain water is caused during heating operation or defrost operation.
1
Choose a place where well drainage is available.
Or provide a groove for drain.
2
Do not provide an upward slope from the unit
to avoid reverse flow of the drain.
3
When dripping drain water is not permissible,
provide a second drain pan under the outdoor unit to
ensure collection of drain water.