OUTDOOR UNITS
2-44
TC-16001-rev.5
Be sure to note the following points when wirings under the unit using conduit tubing.
Tightly secure the power supply wiring using a cable clamp inside the unit.
NOTES:
1. When installing the power supply wiring, use the field-supplied conduit tube and the plate (accessory)
as shown below. The conduit tube can be connected in two direction (front and right side).
Open either side of the knockout-hole for conduit tube.
2. When installing the communication cables, run them through the rubber grommet (accessory).
(Require to make a hole in the rubber grommet)
3. Draw each individual cable through its corresponding hole.
4. Maintain at least 5 inch (127mm) between the power supply wiring and communication cables.
5. Attach the pipe cover to prevent small animals or insects from entering the unit.
6. Prevent cables from touching or rubbing up against refrigerant piping, plate edges, and electrical
components inside the unit.
7. Completely seal the end of conduit tube with sealing materials to prevent the rain from entering the
conduit tube.
8. Create a drainage hole at the lowest part of the conduit tube.
Pipe Cover
Front Side Connection
Plate
(Accessory)
Plate
(Accessory)
Rubber Grommet
(Accessory)
Screw
(Accessory)
Screw
(Accessory)
Conduit Tube
(
φ
3/4 inch (19.05mm))
Pipe Cover
Right Side Connection
Rubber Grommet
(Accessory)
Conduit Tube
(
φ
3/4 inch (19.05mm))