SELECTION DATA
4-4
TC-16001-rev.5
< Result >
Item
Room (1)
Room (2)
Room (3)
Total
Selected Model
HIDM015B21S
HIDM015B21S
HIDM018B21S
(1) ~ (3)
Actual
Capacity
Actual Maximum
Cooling Capacity
Btu/h
11,216
11,216
13,459
35,890
(kW)
(3.3)
(3.3)
(3.9)
(10.5)
Actual Maximum
Heating Capacity
Btu/h
11,630
11,630
13,956
37,216
(kW)
(3.4)
(3.4)
(4.1)
(10.9)
Design
Load
Estimated
Cooling Load
Btu/h
11,000
11,000
13,000
35,000
(kW)
(3.2)
(3.2)
(3.8)
(10.3)
Estimated
Heating Load
Btu/h
11,400
11,400
13,700
36,500
(kW)
(3.3)
(3.3)
(4.0)
(10.7)
(7) Actual Capacity
In the example, the total indoor unit capacity is 48MBH (= 15MBH x 2 + 18MBH),
and outdoor unit capacity is 48MBH.
Therefore, the connected indoor unit capacity ratio is 100%.
a) Actual Capacity of Outdoor Unit
Maximum Actual Capacity of Outdoor Unit
=
1
Outdoor Unit Capacity According to Temperature Condition and Connected IDU Capacity Ratio
×
2
Correction Factor According to Piping Length and Lift
×
3
Correction Factor According to Defrosting Operation (only heating)
×
4
Correction Factor According to Altitude
Maximum Actual Capacity of Outdoor Unit
Cooling = 48,000Btu/h × 1.0 × 0.97 = 35,890Btu/h
Heating = 54,000Btu/h × 0.9 × 0.87 × 0.97 = 37,216Btu/h
b) Actual Capacity of Each Indoor Unit
Actual Capacity of Each Indoor Unit
= Actual Capacity of Outdoor Unit × Each Indoor Unit Capacity ÷ Summation of Indoor Units Capacity
1
2
3
4
Cooling
37 MBH
1.00
-
0.97
Heating
49 MBH
0.90
0.87
0.97
Note
Section 4.2
Section 4.3
Section 4.4
Section 4.5