P5417009-rev.6
29
15
o
CORRECT
INCORRECT
Example for Pipe Support
Secure Liquid Pipes, Low Pressure Gas Pipes and High/Low Pressure Gas Pipes
Outdoor Unit
Indoor Unit
Multi-Kit
Install Horizontally
Installing Pipes: Install at Appropriate Intervals
Treatment for Section
of Fire Prevention
Due to varying chemical properties, gas and liquid pipes
will expand or contract at different rates due to changing
refrigerant temperatures.
Do not fasten gas and liquid pipes together with tape.
Distortion and deformation of the pipes can occur.
Installing Pipes
NOTICE:
Low Pressure Gas Pipe
Liquid Pipe
High/Low Pressure Gas Pipe
Precaution for Installing and Securing Piping
When assembling pipes onsite with hidden elbow or socket joints, provide a service access door to
facilitate close-up examination of interconnecting components.
Table 6.1 Pipe Sizes of Outdoor Unit
Table 6.2 Pipe Sizes of Indoor Unit
inch (mm)
Indoor Unit Capacity
(MBH)
Gas
Liquid
6 - 15
1/2 (12.7)
1/4 (6.35)
18 - 54
5/8 (15.88)
3/8 (9.52)
60 - 72
3/4 (19.05)
3/8 (9.52)
96
7/8 (22.2)
3/8 (9.52)
Model: (H,Y)VAHR_B(3,4)2S
inch (mm)
Outdoor Unit Capacity
(MBH)
Gas
Liquid
Low Pressure
High/Low Pressure
72, 96
7/8 (22.2)
3/4 (19.05)
1/2 (12.7)
120
1-1/8 (28.58)
7/8 (22.2)
1/2 (12.7)
144 - 192
1-1/8 (28.58)
7/8 (22.2)
5/8 (15.88)
216
1-1/8 (28.58)
7/8 (22.2)
3/4 (19.05)
240 - 360
1-3/8 (34.93)
1-1/8 (28.58)
3/4 (19.05)
384 - 432
1-5/8 (41.28)
1-3/8 (34.93)
3/4 (19.05)