36
P5417009-rev.6
(3) When pipe length between outdoor units is 6.6 ft (2m) or more, an oil trap for the gas pipe should be
installed so that no accumulation of refrigerant oil can occur.
● Less than 6.6 ft (2m)
● 6.6 ft (2m) or More
(4) Place the outdoor unit pipe horizontally or with the pipe slanted downward towards the indoor unit side
so that accumulation of refrigerant oil does not occur in the pipe.
(6) Direction of Piping Connection Kit
Place the piping connection kit so it is parallel to the ground (the slope must be 15
o
) as shown
in the figure.
(5) For servicing, if the pipe is installed in front of the outdoor unit, make sure a minimum clearance of
19-11/16 inches (500mm) between the outdoor unit and each piping connection kit. (When the
compressor is replaced, ensure a minimum clearance of 19-11/16 inches (500mm).)
The refrigerant system may be damaged if the slope of the piping connection kit e15
o
.
NOTICE
Less than
6.6 ft (2m)
Less than
6.6 ft (2m)
Less than 6.6 ft (2m)
Less than 6.6 ft (2m)
Less than 32 ft (10m)
Oil Trap
Min. 7-7/8 inches
(200mm)
Oil Trap
Min. 7-7/8 inches
(200mm)
Refrigerant oil accumulates in the pipe.
Indoor Unit Side
Indoor Unit Side
Indoor Unit Side
Indoor Unit Side
Piping
Connection Kit
Piping
Connection Kit
Outdoor Unit
Min.
19-11/16 inches
(500mm)
Outdoor Unit
Outdoor Unit
15
o