P5417009-rev.6
Install a multi-pole main switch with a space of 1/8 inch (3.5mm) or more between each phase.
ATTENTION:
1. When the power supply wiring is longer, select the minimum wiring size that has a voltage drop within 2%.
2. Power supply voltage should be satisfied with the followings.
Supply Voltage:
Rated Voltage 10%
Starting Voltage: Rated Voltage within -15%
Operating Voltage: Rated Voltage 10%
Imbalance between Phases: within 3%
3. Do not connect the ground wiring to gas piping, water pipe, or a lightening conductor.
Gas Piping: An explosion and ignition may occur if there is escaping gas.
Water Piping: There is no effective electrical ground provided when hard vinyl piping is used.
Lightening Conductor: The electrical potential of the earth increases when a lightening conductor is used.