80
P5417009-rev.6
Code
Category
Content of Abnormality
Leading Cause
30
System
Incorrect Connection of
Change-Over Box
Connection of Change-Over Box to Heat Pump System,
Disconnection of Change-Over Box to Heat Recovery System,
Generation1 and 2 Change-Over Boxes are used in the same
system
31
Incorrect Capacity Setting of
Outdoor Unit and Indoor Unit
Incorrect Capacity Setting of Outdoor Unit and Indoor Unit,
Excessive or Insufficient Indoor Unit Total Capacity Code
35
Incorrect Setting of Indoor Unit No.
Duplication of Indoor Unit No. In same Refrigerant Cycle Number
36
Incorrect of Indoor Unit Combination
Indoor Unit is Designed for R22
38
Abnormality of Picking up Circuit for
Protection in Outdoor Unit
Failure of Protection Detecting Device
(Incorrect Wiring of Outdoor PCB)
3A
Outdoor Unit
Abnormality of Outdoor Unit Capacity
Outdoor Unit Capacity > 432MBH
3b
Incorrect Setting of Outdoor Unit Models
Combination or Voltage
Incorrect Setting of Main and Sub Units(s) Combination or Voltage
3d
Abnormal Communication between
Main Unit and Sub Unit(s)
Incorrect Wiring, Disconnect Wire, Breaking Wire, PCB Failure
3E
Abnormal Combination between
Inverter PCB and Outdoor PCB
Incorrect Combination between Inverter PCB and Outdoor PCB
43
Protection
Device
Activation of Pressure Ratio Decrease
Protection
Defective Compression (Failure of Compressor or Inverter, Loose
Power Supply Connection)
44
Activation of Low Pressure Increase
Protection
Overload at Cooling, High Temperature at Heating, Expansion Valve
Locking at Open Position (Loose Connector)
45
Activation of High Pressure Increase
Protection
Overload Operation (Heat Exchanger Clogging, Short Circuit of
Airflow), Pipe Clogging, Excessive Refrigerant, Inert Gas Mixing
47
Activation of Low Pressure Decrease
Protection
Insufficient Refrigerant, Piping Clogging, Expansion Valve Locking
at Close Position (Loosen Connector)
48
Activation of Inverter Overcurrent
Protection
Overload Operation, Compressor Failure
51
Sensor
Abnormal Inverter Current Sensor
Current Sensor Failure
53
Inverter
Inverter Error Signal Detection
Driver IC Error Signal Detection (Protection for Overcurrent, Voltage
Decrease, Short Circuit), Instantaneous Overcurrent
54
Abnormality of Inverter Fin Temperature Abnormal Inverter Fin Thermistor,
Heat Exchanger Clogging, Fan Motor Failure
55
Inverter Failure
Inverter PCB Failure
57
Fan Controller
Activation of Fan Controller Protection
Driver IC Error Signal Detection (Protection for Overcurrent, Voltage
Decrease, Short Circuit), Instantaneous Overcurrent
5A
Abnormality of Fan Controller Fin
Temperature
Fin Thermistor Failure, Heat Exchanger Clogging, Fan Motor Failure
5b
Activation of Overcurrent Protection
Fan Motor Failure
5C
Abnormality of Fan Controller Sensor
Failure of Current Sensor (Instantaneous Overcurrent, Increase of
Fin Temperature, Voltage Decrease, Grand Fault, Step-Out)
A1
External Input Detection of External Abnormality
Input Signal by External Abnormality Detection Setting
b0
Indoor Unit
Incorrect Setting of Unit Model Code
Incorrect Setting of Indoor Unit Model
b1
Incorrect Setting of Unit and
Refrigerant Cycle Number
64 or More Number is Set for Address or Refrigerant Cycle
b2
Abnormality of EEPROM
EEPROM failure, Incorrect Data of EEPROM
b5
Incorrect Indoor Unit No. Setting
There are 17 or More Non-Corresponding to H-LINK II Units are
Connected to One System.
b6
Abnormal Communication between
Indoor PCB and Indoor Fan Controller
Communication Failure, Disconnected Communication Cable,
Abnormal Connection
C1
Change-Over
Box
Incorrect Change-Over Box Connection 2 or More Change-Over Boxes are Connected between
Outdoor Unit and Indoor Unit
C2
Incorrect Indoor Unit Connection Number
9 or More I.U. Connected to Single Branch Type Change-Over Box,
7 or More I.U. Connected per a branch of Multiple Branch Type
Change-Over Box
C3
Incorrect Indoor Unit Refrigerant Number
Setting
Indoor Units of Different Refrigerant Cycle Number are Connected
to Change-Over Box
C5
Incorrect Connection Port Setting
Indoor Unit is connected to a port that is set to not used for Multiple
Branch Type Change-Over Box
EE
Compressor
Compressor Protection Alarm
(It can not be reset from Wired
Controller)
This alarm code appears when the following alarms* occurs three
times within 6 hours.
*02, 07, 08, 39, 43 to 45, 47