WARNING
DO NOT PROCEED WITH OPERATION OF THIS FIREPLACE
UNLESS BURNER "CYCLES" ON/OFF WITHOUT DELAYS!
GAS INPUT RATE VERICATION REQUIREMENTS
Natural Gas Applications Gas Input Rate Verification Procedures
Verify Main Orifice Size. The main orifice body has the orifice hole size stamped on it. NG orifice size shall be
#44” (Rear Burner) and # 49 (Front Burner) for all elevations.
Verify that the Manifold Gas Pressure is within 3.5" WC +/- 1/8".
Once setup, read the main home gas supply meter reading.
Write the initial reading here >> Initial Gas Meter Reading _______________
Turn OFF all other appliances and their pilot flame in the home.
Run this appliance for a period of 30 minutes on maximum flame size. Turn off main burner and pilot flame.
Read the main home gas supply meter reading after the 30 minutes of burn time.
Write the reading here >> Final Gas Meter Reading _______________
Calculate the following:
FINAL GAS METER READING - INITIAL GAS METER READING...Subtract Initial Gas Meter from Final Gas
Meter Reading. This will yield the number of Therms used during the 30 minute burn time.
Multiply the result in Item 11 by 100,000.
Multiply the result in Item 12 by 2. Write down the Result here >>_________________
The result in item #13 shall be at least maximum Input Rate (34,000 Btu) for altitudes below 2000 Feet. For alti-
tudes higher than 2000 feet, the result in item #13 shall be at least 33,000 Btu.
LPG Applications Gas Input Rate Verification Procedures
Verify Main Orifice Size. The main orifice body has the orifice hole size stamped on it. LPG orifice size shall be
3/64” (Front and Rear Burners) for 0-2000 feet elevation and 3/64” Front Burner and #55 Rear Burner for eleva-
tions exceeding 2000 feet.
Verify that the Manifold Gas Pressure is within 10.0" WC +/- 1/8".
CHECKING FOR NORMAL BURNER (S) IGNITION CHARACTERISTICS
Once the conversion to LPG and all the above steps have been completed, light the main burners.
Use Remote Transmitter to turn on Pilot Light and burners. Main burner should now light IMMEDIATELY and flame
should not "lift" off burner. If there is any delay in ignition or if flame is "lifting off" burner, turn off burner and carefully
check for proper installation of logs/coals, vent system and proper pilot flame impingement on burner. Logs or coals must
not block pilot flame or main burner flame. Vent system must be leak proof.
ATTACHING LPG CONVERSION LABELS AND HIGH ALTITUDE DERATION LABEL
Two printed informational labels are included with the LPG Conversion Kit. Attach these two labels to the back surface of
the Serial Number Plate that is located in the convection air cavity below the firebox. If you are derating this appliance at a
high altitude, also attach the High Altitude Deration Label, supplied in the Owner’s Manual Packet, to this same surface.
Prior to attaching the labels, fill in all the information that is requested in these labels.
For installations from 610-1370 meters (2000-4500 ft.) the orifice sizes (DMS) for Natural Gas are #44(rear)
and #49(front) and Propane Gas are $55(rear) and 3/64”(front), respectively. See data plate for additional in-
formation. For high altitude installations consult the local gas distributor or the authority having jurisdiction for
proper rating methods. If the installer must convert the unit to adjust for varying altitudes, the information
sticker must be filled out by the installer and adhered to the appliance at the time of conversion."
«Cet appareil est equipé pour des altitudes compries entre 0 et 2000 pieds (0-610 m) seulement»
This appliance has been converted for use at an altitude of ______________
Orifice size _______________
Manifold Pressure ________________
Input (Btu/h)_______________
Fuel Type _______________________
Date of conversion _________
Converted by _____________________
«Cet appreeil a été converti au ____
Injecteur ________
Pression à la tubulure d'alimentation _____________
Déoit calorifique ______________