background image

www.johnsonsystems.com

8

4.  SET CS 

Set the DMX channel patch for a CS-DMX control station. 

 

PATCH 

Transfers the patch from CS-IPRO memory to control station memory.

 

 

The DMX channel patch data in the programmer memory is sent and saved into a 

CS-DMX control station. The total transfer time to set the patch is approximately 110 

milliseconds.

 

 

Point the CS-IPRO infrared LED window directly at the CS-DMX infrared LED 

window, within 12" (30 cm). 

   SET CS 

Press EXECUTE to set the CS-DMX control station patch.

 

SENDING 

Displayed briefly while data is being sent from the CS-IPRO.

 

OKAY 

Indicates data has been successfully transferred.

 

COMM ERR 

Indicates a communication error has been detected. Try again.

 

CRC ERR! 

Indicates a CRC data checking error has been detected. Try again.

 

KEY ERR! 

Indicates a security key error. Try again.

 

INVALID 

Indicates the security key data contains an invalid range. Try again.

5.  GET CS 

Get the existing DMX channel patch from a CS-DMX control station.

 

PATCH 

Transfers the patch from control station memory to CS-IPRO memory.

  

The existing DMX channel patch is read from the CS-DMX control station and loads 

the patch into the CS-IPRO transfer buffer. The data is checked and verified and 

then loaded into the CS-IPRO memory. The patch can then be viewed in the CHECK 

PATCH menu or modified in the EDIT PATCH menu.

 

 

Point the CS-IPRO infrared LED window directly at the CS-DMX infrared LED 

window, within 12" (30 cm). 

 

GET CS 

Press EXECUTE to get the CS-DMX control station patch.

 

CHECKING 

Displayed briefly while data is being read and transferred.

 

OKAY 

Indicates data has been successfully transferred to the CS-IPRO.

 

COMM ERR 

Indicates a communication error has been detected. Try again.

 

DATA ERR 

Indicates a data error has been detected. Try again.

6. SAVE 

Save the DMX channel patch into the removable EEPROM Memory Module.

 

PATCH 

Saves the patch in the CS-IPRO memory only.

 

 

The DMX channel patch saved in the CS-IPRO memory is saved into the removable 

EEPROM Memory Module. Note that previously saved DMX channel patch data in 

the EEPROM Memory Module will be overwritten.

 

SAVE 

Press EXECUTE to enter the menu and save the DMX channel patch.

 

SURE ??? 

Press EXECUTE again to save the DMX channel patch. Are you sure?

 

DONE !!! 

Indicates the DMX channel patch has been successfully saved.

 

CRC ERR! 

Indicates a CRC data checking error has been detected. Try again.

 

TYPE ERR 

Indicates the wrong type of EEPROM memory module has been detected.  

 

MEM ERR! 

Indicates a defective EEPROM memory module has been detected.

 

NO MEM ! 

Indicates an EEPROM memory module has not been detected (not installed).

 

 

Automatically exits the menu when the patch has been successfully saved.

7. LOAD 

Load the DMX channel patch from the removable EEPROM Memory Module.

 

PATCH 

Loads and saves the patch into the CS-IPRO memory.

 

 

The DMX channel patch saved in the EEPROM Memory Module is loaded and saved 

into the CS-IPRO memory. Note the previous DMX channel patch data in the CS-

IPRO memory will be overwritten. 

 

LOAD 

Press EXECUTE to enter the menu and load the DMX channel patch.

 

SURE !!! 

Press EXECUTE again to load the DMX channel patch. Are you sure?

 

DONE !!! 

Indicates the DMX channel patch has been successfully loaded.

 

CRC ERR! 

Indicates a CRC data checking error has been detected. Try again.

 

TYPE ERR 

Indicates the wrong type of EEPROM memory module has been detected.  

 

MEM ERR! 

Indicates a defective EEPROM memory module has been detected.

 

NO MEM ! 

Indicates an EEPROM memory module has not been detected (not installed).

 

 

Automatically exits the menu when the patch has been successfully loaded.

Summary of Contents for CS-IPRO

Page 1: ...rta Canada T2G 5M1 tel 403 287 8003 fax 403 287 9003 e mail info johnsonsystems com website www johnsonsystems com User Manual CS IPRO Wireless Hand Held Programmer for CS DMX Series Control Stations JOHNSON SYSTEMS INC www johnsonsystems com ...

Page 2: ...f this manual can be downloaded at http www johnsonsystems com cs_ipro_user_manual htm Table of Contents Warranty 2 User Manual Copies 2 Introduction 3 Specifications 3 Battery Replacement 4 Security 4 User Interface 4 System Status LCD Display 5 Quick Programming Reference to System Configuration Menu Items 6 Detailed Programming of System Configuration Menu Items 7 Typical Application Procedures...

Page 3: ...rol station infrared LED window is located on the front between the master slider and slider 1 The maximum range for sending and receiving data between the CS IPRO and CS DMX control stations is 12 30 cm The CS IPRO is capable of printing out various configuration settings when used in conjunction with a hand held infrared printer Johnson System Inc Part Number JS IP The maximum range for sending ...

Page 4: ...and easy to navigate All configuration settings are automatically stored into an on board internal EEPROM LCD Display The LCD display is capable of displaying 2 lines of 8 characters The LCD backlight automatically turns on when there is activity and turns off after two 2 minutes of inactivity The LCD contrast can be easily adjusted for optimum viewing Refer to menu item LCD VIEW ADJUST on page 8 ...

Page 5: ...less the configuration menu items are being accessed The bottom line of the LCD display shows the current status In normal run mode it will show REMOTE If a low battery level 2 0V to 2 1V is sensed it will show LOW BAT indicating the batteries need to be replaced If a critical battery level 1 9V or less is sensed it will show CRITICAL on the top line and PWR DOWN on the bottom line for 5 seconds a...

Page 6: ...ble EEPROM Memory Module PATCH Loads and saves the patch into the CS IPRO memory 8 EEPROM View the type of EEPROM memory module plugged into the CS IPRO IPRO X 9 EEPROM Load new firmware into the CS IPRO via the EEPROM memory module FW LOAD 10 EDIT KEY Edit the security key for the CS IPRO SECURITY 11 SET KEY Set the security key for a CS DMX control station SECURITY 12 GET KEY Get the existing se...

Page 7: ...cates the selected slider SS DMX channel CH and patch P status 01 000 The pointer indicates the selected slider to be edited 12 000 Press MENU to select the slider number from 01 to 12 12 000 Press EXECUTE to edit the DMX channel s to patch to the selected slider 12 000 Press EXECUTE to move the cursor to the right under the digit to be edited 12 000 Press ESCAPE to move the cursor to the left or ...

Page 8: ... been detected Try again DATA ERR Indicates a data error has been detected Try again 6 SAVE Save the DMX channel patch into the removable EEPROM Memory Module PATCH Saves the patch in the CS IPRO memory only The DMX channel patch saved in the CS IPRO memory is saved into the removable EEPROM Memory Module Note that previously saved DMX channel patch data in the EEPROM Memory Module will be overwri...

Page 9: ...LED This menu is disabled for inadvertent use Proceed to enable ENABLED Press and hold MENU and MENU at the same time for 4 5 seconds MEMCHECK Automatically checks the EEPROM memory module for firmware type CRC TEST Automatically does a CRC test on the firmware code in the EEPROM The CRC test in progress VER X X Displays the firmware version on the EEPROM memory module UPDATE Press EXECUTE to proc...

Page 10: ... from a CS DMX control station To get the security key from a CS DMX control station the security jumper on the control station must be installed in the disabled position Getting the existing security key from a CS DMX control station automatically loads the 8 digit security key into the CS IPRO memory Point the CS IPRO infrared LED window directly at the CS DMX infrared LED window within 12 30 cm...

Page 11: ...d slider SS number 01 to printout SS ALL Press MENU to select the slider number from 01 to 12 or ALL to print PRINTING Press EXECUTE to printout the DMX channel patch for the selected slider s DONE Displayed briefly to indicate data has been sent to the hand held printer Press ESCAPE to exit the menu 19 LCD VIEW Adjust the contrast of the LCD Display for optimum viewing ADJUST LCD VIEW Press EXECU...

Page 12: ... D 23 1cm x 7 0cm x 5 1cm CS SA ENT2B 1 gang 2 button on off entrance station with adjustable on voltage for stand alone applications 5 x 18 AWG 1 gang 1 80 W x 2 75 H x 2 00 D 4 6cm x 7 0cm x 5 1cm CS SA ENT3B 3 button entrance station w on preset and off 6 x 18 AWG 1 gang 1 80 W x 2 75 H x 2 00 D 4 6cm x 7 0cm x 5 1cm CS IPRO Hand held Infrared Station Programmer 2 75 W x 4 95 H x 1 00 D 70cm x ...

Reviews: