035-17443-000 Rev. A (800)
Unitary Products Group
5
b.
Not less than the sum of the areas of all vent con-
nectors in the confined space.
3.
Louvers, Grilles and Screens
a.
In calculating free area, consideration must be given
to the blocking effects of louvers, grilles and
screens.
If the free area of a specific louver or grille is not known, refer
to Table 2 to estimate free area.
NOTE: If mechanically operated louvers are used, a means
to prevent main burner ignition and operation must be
provided should louvers close during startup or operation.
Special Combustion and Ventilation Considerations
Operation of a mechanical exhaust, such as an exhaust fan,
kitchen ventilation system, clothes dryer or fireplace may cre-
ate conditions requiring special attention to avoid unsatisfac-
tory operation of gas appliances.
Specially Engineered Installations
The above requirements shall be permitted to be waived
where special engineering, approved by the authority having
jurisdiction, provides an adequate supply of air for combus-
tion, ventilation and dilution of flue gases.
Combustion Air Quality
The recommended source of combustion air is to use the out-
door air supply. Excessive exposure to contaminated com-
bustion air will result in safety and performance related
problems. However, the use of indoor air in most applications
is acceptable, except as follows:
1.
If the furnace is installed in a confined space it is recom-
mended that the necessary combustion air come from
the outdoors by way of attic, crawl space, air duct or
direct opening.
2.
If outdoor combustion air is used, there must be no expo-
sure to the installations or substances listed in #3 below.
3.
The following types of installations may require OUT-
DOOR AIR for combustion, due to chemical exposure.
a.
Commercial buildings
b.
Buildings with indoor pools
c.
Furnaces installed in laundry rooms
d.
Furnaces installed in hobby or craft rooms
e.
Furnaces installed near chemical storage areas
f.
Permanent wave solutions
g.
Chlorinated waxes and cleaners
h.
Chlorine based swimming pool chemicals
i.
Water softening chemicals
j.
De-icing salts or chemicals
k.
Carbon tetrachloride
l.
Halogen type refrigerants
m. Cleaning solvents (such as perchloroethylene)
n.
Printing inks, paint removers, varnishes, etc.
o.
Hydrochloric acids
p.
Cements and glues
q.
Antistatic fabric softeners for clothes dryers
r.
Masonry acid washing chemicals
TABLE 1: UNIT CLEARANCES TO COMBUSTIBLES (ALL DIMENSIONS ARE IN INCHES)
ALL SURFACES IDENTIFIED WITH THE UNIT IN AN UPRIGHT CONFIGURATION
APPLICATION
TOP
FRONT
REAR
LEFT
SIDE
RIGHT
SIDE
FLUE
FLOOR /
BOTTOM
CLOSET
ALCOVE
ATTIC
LINE
CONTACT
UPFLOW / HORIZONTAL MODELS - UPFLOW APPLICATION
UPFLOW
1
6
0
0
3
6
COMBUSTIBLE
YES
YES
YES
NO
UPFLOW B-VENT
1
3
0
0
0
1
COMBUSTIBLE
YES
YES
YES
NO
UPFLOW / HORIZONTAL MODELS - HORIZONTAL APPLICATION
HORIZONTAL
1
6
0
0
3
6
COMBUSTIBLE
NO
YES
YES
YES
1
HORIZONTAL
B-VENT
1
3
0
0
0
1
COMBUSTIBLE
NO
YES
YES
YES1
1.
Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of
the furnace jacket and building joists, studs or framing.
TABLE 2: ESTIMATED FREE AREA
Wood or Metal
Louvers or Grilles
Wood 20-25%
Metal 60% - 70%
1
1.
Do not use less than 1/4 in. mesh
Screens
2
2.
Free area of louvers and grilles varies widely; installer
should follow louver or grille manufacturer’s instruc-
tions.
1/4 in. mesh or larger 100%