Fig. 15: Screw delicately the ionising tube
holding on to the base (green part).
If the operation is difficult to perform, pull
slightly the earthing spring so that it is not in
contact with the surface of the tube.
ATTENTION: do not overtighten the screw
after reaching its end stop.
Check that the earthing spring
is in contact with the outer
mesh once the ionising tubes
have been screwed back into
place. Otherwise contact the
manufacturer.
Fig. 16: Reposition the device
JO
NIX
VMC
by inserting the ionising tubes horizontally
into the specific hole and screw the 2
screws that secure the module to the wall.
Fig. 17: Reinsert the power supply plug
and all other plugs in the appropiate sockets
of the
JO
NIX
VMC
module.
Switch on the moduleby turning the On/Off
switch to I.
Verify the functioning of the device, it has to
be hear a light sizzle coming from the tubes.
Reset the alarm reporting
through corresponding
entrance.
Failure to replace the ionising tubes leads to a decrease in system performance
until they actually break. From that moment on, they will have no more effect on
treated air.