-5-

11

. Loop powered 4-20mA transmitter. This amplifier is

equipped with an on-board loop powered transmit-

ter that can transmit the true actuator output shaft

position in 4-20mA units. The transmitter requires

an external 12-36 Vdc regulated power supply, load

resistor, and indicator; available from Jordan

Controls at extra charge. After wiring is completed

per the wiring diagram shipped with the actuator,

adjustment is as follows: Apply a command signal to

the actuator at the minimum value. For 4-20mA

systems this would normally be 4 mA. After the

actuator moves to position and stops, adjust the pot

labeled 4mA until the indicator displays 4mA. Then

apply a 20mA command signal and wait for the

actuator to move and stop. Then adjust the pot

labeled 20mA until the indicator displays 20mA.

Some interaction of the above pot settings will

require repeating this procedure until proper

accuracy is achieved. Adjustment is complete.

12

. Loss of 4-20mA signal. In the event of a loss of

current command signal (“LOS”), the servo ampli-

fier can be programmed to either lock in place or

go to a preset position.  Referring to the DIP

SWITCH TABLE, select one option and position the

DIP SWITCH accordingly.  If “move to preset”

option is selected, the preset position must be

adjusted now.

With the servo amplifier in normal operation,

remove the positive command signal wire from the

amplifier.  The LED labled LOS lights, indicating a

loss of command signal, and the actuator will move

to the preset LOS pot setting.  Slowly adjust the

LOS pot until the actuator shaft is in the position

desired when loss of command signal occurs.

Reconnect the command signal.  Adjustment is

complete.

Note

: With Dip Switch 4 in its manual position,

momentary switches S1, S2 and S3 can be used to

manually stroke the actuator.  Depressing S1 will cause

the actuator to move in one direction, and depressing

S2 will cause the actuator to move in the opposite

direction.  The end of travel limit switches in the

actuator will protect against overtravel in either

direction.

With Dip Switch 4 in its manual or automatic

position, depressing S3 will immediately stop actuator

travel.

Switch

Position

Function

On

4-20mA Command Signal

Off

Not Using 4-20mA Command

On

Voltage Command Signal

Off

Current Command Signal

On

Loss of Signal - Park in Place

Off

Loss of Signal - Go to Set Point

On

Auto Operation

Off

Manual Operation

On

0-5 Vdc Command Signal

Off

0-10 Vdc Command Signal

On

4-20mA Remote Feedback

Off

Pot Feedback

On

Not Used

Off

Not Used

On

Not Used

Off

Not Used

AD-7830 DIP SWITCH TABLE

1

2

3

8

4

5

6

7

Summary of Contents for AD-7830

Page 1: ...anual 2 General Description 3 Actuator Compatability 3 Basic Models 3 Specifications 3 Installation Wiring 3 Set up and Calibration 4 5 Component Location 6 Troubleshooting Guide 7 Typical Wiring Diagrams 8 Major Dimensions 9 10 IM 0606 Due to wide variations in the terminal numbering of actuator products actual wiring of this device should follow the print supplied with the unit ...

Page 2: ...e actuator WARNING SHOCK HAZARD Installation and servicing must be performed only by qualified personnel WARNING ELECTROSTATIC DISCHARGE This electronic control is static sensitive To protect the internal components from damage never touch the printed circuit cards without using electrostatic dis charge ESD control procedures RECEIVING INSPECTION Carefully inspect for shipping damage Damage to the...

Page 3: ...ce 0 to 5 0 to 10 Vdc or optionally using EC 10844 for 10 to 10 Vdc command into a 100k ohm impedance Position feedback signal 1000 ohm potentiometer or 4 20 mA switch selectable 4 to 20 mA feedback is normally used for remote amplifier installations Other inputs Position limit switches 2 and torque or thrust limit switches 2 from actuator Auto Manual switch with increase and decrease capabiity No...

Page 4: ... switch Next apply command signal at maximum input value For 4 20mA systems this would normally be 20mA Adjust pot labeled SPAN to move actuator position to correspond with maximum desired position without actuating the end of travel limit switch Some interaction of the above pot settings will require repeating this procedure until proper accuracy is achieved 7 SPEED adjust pot must be set to limi...

Page 5: ...accordingly If move to preset option is selected the preset position must be adjusted now With the servo amplifier in normal operation remove the positive command signal wire from the amplifier The LED labled LOS lights indicating a loss of command signal and the actuator will move to the preset LOS pot setting Slowly adjust the LOS pot until the actuator shaft is in the position desired when loss...

Page 6: ...ion Amplifier Power Board Enclosed in Metal Case Customer Interface Board 50 Pin Ribbon Input Voltage 1 Blue Box Driver Board 68C 038504 001 2 Interface Board 68C 035606 001 3 Ribbon Cable 25A 035285 002 Spare Parts List ...

Page 7: ...perly adjusted a Adjust speed pot as required but not faster than catalog ratings b Bal pot needs adjustment b Adjust Bal pot as required a Input voltage selector switch not in correct position a Correct position as required b 180 Vdc actuators must have 240 Vac input to amplifier b Insure proper power supply is available c Amplifier output voltage jumper selector in wrong position c Correct jumpe...

Page 8: ...t actuator with 24 Vdc loop power when amplifier distance from actuator exceeds 50 feet of wiring Notes 1 240 Vac input is required where actuator nameplate voltage is 180 Vdc 2 24 Vdc power supply is required 3 When using external Auto Manual switch DIP SWITCH SW1 4 must be set for manual operation on amplifier Due to wide variations in terminal numbering of actuator products actual wiring should...

Page 9: ... 9 AD 7830 P Amplifier Mounted on a Panel Major Dimensions AD 7830 R73P Retro fit for AD 7300 Series ...

Page 10: ...als and position torque limit switches Major Dimensions Remote Mount AD 7830 E Installed in remote enclosure NEMA 4 These dimensions are subject to change without notice and should not be used for preparation of drawings or fabrication of installation mounting Current installation dimension drawings are available upon request JORDAN CONTROLS INC 5607 West Douglas Avenue Milwaukee Wisconsin 53218 P...

Reviews: