background image

12

139405_A  CF 

3

 BF

 3 

 

D

E

Gas Installation

Gas installation must only be performed by qualified 

personnel. It is important to adhere to national and local 

regulations that apply. In the UK these include BS5440 

Parts 1 and 2, and BS5871 in Ireland.

The LPG gas container must be stored/installed ac-

cording to national regulations. The gas container must 

have a pressure regulator that reduces the pressure to the 

required level. See technical data on page 4 for gas type 

and pressures before connecting to the appliance. 

The appliance must not be exposed to pressure above 

55 mbar (5,5 kPa) during pressure testing. 

Gas tubes must be made of steel (DIN 2448/1629, DIN 

2458/1626, DIN 2440, DIN 2441) or copper (DIN 2110). 

For practical reasons, the vent system should be 

installed before the appliance is connected to the gas 

supply. 

The stove is supplied with a 3/8” to 8mm compression 

union. The gas valve has a 3/8” NPT threaded connection. 

All tube connections must be approved and the gas 

pipeline must have an approved shutoff valve.  Only use 

approved sealing agent (tape) at all the pipe connections. 

When the pipe sections have been assembled and con-

nected to the appliance, open the gas supply and light the 

appliance (see lighting instructions). Perform a tightness 

test on all the pipe connections.

Commissioning

Testing Gas Pressure

Correct gas pressure is important for the safe use of gas in 

the appliance. It is important that the correct gas pressure 

is set during the installation of the appliance. 

The gas valve is equipped with outlets for the test-

ing of gas pressure. The outlets are located at the front of 

the valve below the ON/OFF/Pilot knob. The outlets are 

marked as shown in fig. 15. 
Outlet D: For gas pressure to the valve (volume of gas to 

the valve) See technical data. 

Outlet E: For gas pressure from the valve (volume of gas 

coming out of the valve to the burner). 

C:  Regulator - Always test the gas pressure with the valve 

regulator knob on High (Hi). 

Loosen the screw in the outlet and attach the tube from 

the manometer to the outlet. Remember to tighten the 

screw when the testing is completed and test for leaks at 

the outlets with test fluid.
Required gas pressure from the vent (Outlet E) is displayed 

in the table below. (Note that the installer is required to 

operate the appliance for at least 20 minutes before mea-

suring the burner pressure.)

GAS TYPE                       Burner Pressure (Hot), mbar     

   

Natural Gas  (G20)                    9.10 mbar
Propane     (G31)                        25.9 mbar

Figure 15. Valve pressure tap locations.

C

Summary of Contents for GF 3 BF

Page 1: ...e or other flammable vapors and liq uids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any...

Page 2: ...ssociated with the repair of gas controls plumb ing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enameled su...

Page 3: ...6 5 User Information 14 6 Troubleshooting 16 7 Parts Illustrations and Lists 19 8 Service Record 23 THIS OWNER S MANUAL PROVIDES INFORMATION TO ENSURE SAFE INSTALLATION AND EFFICIENT DEPENDABLE OPERA...

Page 4: ...Burner Injector Marking 39 53 Pilot Injector Marking 51 30 Maximum Gas Consumption at Full Rate m3 h at 15 C 1013 25mbar 0 714 0 282 Maximum Gas Consumption at Full Rate kg h at 15 C 1013 25mbar 0 53...

Page 5: ...trol cover and control switch Care should be taken not to touch unit when it is in operation WARNING If you detect an odour of gas Do not light the Stove or any other appliance Do not use electrical s...

Page 6: ...d on carpet vinyl linoleum or other combus tible material Minimum dimensions of the floor plate 580 x 435 mm as in fig 2 J tul can supply floor plates in a variety of colors Firewall Requirements The...

Page 7: ...erminal which is supplied attached with 600mm of flue pipe The 600mm terminal section may be cut to up to 300mm if required 2 Flue arrangement for horizontal termination Fig 6b When the horizontal len...

Page 8: ...ations 400mm Max This arrangement can only be made using kit M82671 The maximum permissible horizontal length is 400mm This length is supplied attached to the terminal Fig 6 a Fig 6 b Fig 6 c Fig 6 d...

Page 9: ...ngth is 600mm or less Vent restrictor position is D 2 Flue arrangement for horizontal termination when horizontal length is greater than 600mm Vent restrictor position is D 3 Flue arrangement for vert...

Page 10: ...the peg as in fig 11 3 Place the left log on the pegs as in fig 12 4 Install middle log on the appropriate pegs shown in fig 13 5 Position embers loosely and maintain 6 mm clearance from the burner sk...

Page 11: ...gure 11 Install right log Figure 12 Install left log Figure 13 Install middle log 1 4 6 mm 1 4 6 mm Pilot Assembly KEEP CARRY OVER PORTS CLEAR PN 220730 PN 220728 PN 220729 Figure 14 Spread ember ston...

Page 12: ...con nected to the appliance open the gas supply and light the appliance see lighting instructions Perform a tightness test on all the pipe connections Commissioning Testing Gas Pressure Correct gas p...

Page 13: ...Flame above 2 Cleaning the glass 3 The gasket around the glass must be inspected annu ally for wear and replaced if necessary 4 Check if the textured embers need to be replaced 5 Look for soot It cou...

Page 14: ...t the appliance may emit a harmless non toxic odour It is recommended that the room should be thoroughly ventilated by opening doors or windows during first time use The gas is not toxic but the room...

Page 15: ...paint and lubrication used in the production process See section Odours when using the stove for the first time Adjusting the Heat Setting Heat and flame size can be adjusted by turning the regu lato...

Page 16: ...t a metal piece and the control knob red mark on the spark igniter is finally pushed to the bottom B If not replace the Piezo spark ignitor Fuel Gas Correct gas pressure is important see the section a...

Page 17: ...r the valve even if the pressure is OK at outlet E You should therefore always check for leakage Thermocouple Fig 23 and Thermopile Fig 24 A thermocouple is in principle a thermal generator and consis...

Page 18: ...he ON OFF STAT switch is connected 10 Turn the control knob on the valve to ON and turn the ON OFF STAT switch to ON At this point the multi meter should show more than 300 mV 11 If a thermostat or re...

Page 19: ...3 Figure 26 NOTE THE GAS CONTROL VALVE ASSEMBLY IS MOUNTED AT THE CENTER FRONT OF ALL STOVES NOTE THE GAS CONTROL VALVE ASSEMBLY IS MOUNTED AT THE CENTER FRONT OF ALL STOVES J tul GF 3 BF 3 Illustrat...

Page 20: ...Block 220614 20 Gas Line 5 16 x 18 Flex 154372 21 Orifice Holder Straight 129643 22 Glass Gasket Replacement Kit 155599 23 Glass Panel Ceramic 220576 24 Glass Gasket 7 16 Tadpole 6 ft 129124 25 Glass...

Page 21: ...21 139405_A CF 3 BF 3 Figure 27 Approved Vent Components M82678 M82652 M82650 M82653 M82654 M82668 M87379 M87913 M82656 M82657 M30170 M82667...

Page 22: ...22 139405_A CF 3 BF 3 100 170mm L 400mm Figure 27a Approved Vent Components M82655 M82671 M87196 M82661...

Page 23: ...ervice year 4 Sign Company Date Service details Annual service year 5 Sign Company Date Service details Annual service year 6 Sign Company Date Service details Annual service year 7 Sign Company Date...

Page 24: ...continual product development Consequently products may differ in speci fication color or type of accessories from those illustrated or described in various publications March 9 2011 139405_A J tul A...

Reviews: