background image

 

 

JOVYTEC PE / PME 

100000004673 

 - 14 -

 

6.1.3 

Displaying UPS status 

If no button is pressed within a certain time, the UPS displays one of the following operating modes. 
 

Display 

Description 

LED 

Line  Mode 

UPS running in online mode 

LED ON-LINE lit 

High Efficiency 

UPS running in bypass mode (high-efficiency mode) 

LED BYPASS lit 

Manual Bypass 

UPS running statically through bypass 

LED BYPASS lit 

Battery Mode  

UPS supplying consumers through battery (see note) 

LED ON-BAT lit 

 
 

NOTE: 

When running in battery mode, the UPS sounds a tone. Refer to the section on function description. 
No sounds are emitted during the battery test. 
 

 
 

6.1.4 

Displaying UPS values 

To review the UPS values, press and hold the <ENTER> button for about 2 seconds.  
Then press then <ENTER> button repeatedly until the desired value is shown in the display. 
The display reverts to showing the UPS status after a few seconds. 
 

Display 

Description 

O/P VOLT = xxx.xV 

Output voltage [V] 

O/P FREQ=xx.x HZ 

Output frequency [Hz] 

I/P VOLT=xxx.xV 

Input voltage [V] 

I/P FREQ=xx.x HZ 

Input frequency [Hz] 

BAT VOLT= xx.xV 

Battery voltage [V] 

O/P LOAD%=xx% 

Percentage of load capacity used [%] 

O/P W=xW 

Active power at output [W] 

O/P VA=xVA 

Output power [VA] 

O/P CURR =x.xA 

Output current [A] 

BACKUP TIME=xxxM 

Available backup time [minutes] 

BAT CHARG=xx% 

Approximate battery charge level [%] 

TEMPERATURE=xxC 

Approximate temperature inside UPS [°C] 

BAT PACK NUM=x 

Configured number of external battery cases 

RATING=  xK    VA 

Rated power 

CPU VERSION   xx.xx 

Firmware version 

 

6.1.5 

Serial interface 

The serial interface can be used together with the included software and included serial data cable. Alternatively 
an optional SNMP adapter may be connected here. 

The data cable is intended for directly connecting the UPS to a PC or an (optional) SNMP adapter. 

 

NOTE: 

The included software is free but corresponding support incurs a fee. 
 
 

 

 

 

i

i

Summary of Contents for JOVYTEC PE 1000 VA

Page 1: ...100000004673 W rtsil JOVYATLAS GmbH Fennenweg 4 26844 Jemgum Germany www jovyatlas de Tel 49 0 4958 9394 0 Fax 49 0 4958 9394 10 Operating Manual JOVYTEC PE PME 1000 1500 2000 3000 VA...

Page 2: ...of delivery for products of the electronics industry as well as our general sales conditions We reserve the right to make changes to these instructions in particular as regards the technical data ope...

Page 3: ...E short version only 10 5 1 6 2000VA JOVYTEC PME short version 100V 120V only 11 5 1 7 3000VA JOVYTEC PME short version only 11 5 1 8 3000VA JOVYTEC PME short version 100V 120V only 11 5 1 9 RS 232 in...

Page 4: ...JOVYTEC PE PME 100000004673 4...

Page 5: ...batteries which include AGM and gel batteries are often termed maintenance free batteries The maintenance free feature only relates to the fact that distilled water cannot be topped up and the acid l...

Page 6: ...faces RS 232 USB serial interfaces for reading UPS data standard SNMP adapter for remote monitoring data exchange via a LAN connection option Relay card with alarm messages for industrial remote monit...

Page 7: ...voltage beyond 10 or 15 if configured accordingly of nominal voltage Input frequency beyond 3 Hz threshold You can activate this operating mode on the control panel 3 2 2 Free run mode Free run mode a...

Page 8: ...tems Note that you must insert it into a slot as far as it will go Refer to the technical data for conditions concerning the setup location 5 Installation This model of UPS either comes with a battery...

Page 9: ...USB OPTIONAL USB socket optional INTERFACE OPTIONAL Interface slot for relay card SNMP adapter etc optional EPO Input for UPS electronic power off RS 232 Data signal NETWORK TRANSIENT PROT Ethernet f...

Page 10: ...JOVYTEC PE PME 100000004673 10 5 1 3 1000VA 1500VA JOVYTEC PME 5 1 4 2000VA 3000VA JOVYTEC PME 5 1 5 2000VA JOVYTEC PME short version only...

Page 11: ...JOVYTEC PE PME 100000004673 11 5 1 6 2000VA JOVYTEC PME short version 100V 120V only 5 1 7 3000VA JOVYTEC PME short version only 5 1 8 3000VA JOVYTEC PME short version 100V 120V only...

Page 12: ...ose of a relay card The 3 possible signals are listed in the table below PIN 6 to 9 Type SUB D9 socket Pin no Signal name Signal direction in relation to UPS Function 2 TxD Output Transmit data 3 RxD...

Page 13: ...it when UPS in bypass mode FAULT LED red Lit if there is an internal fault 6 1 2 Buttons Description of buttons on control panel Buttons Description ON OFF On off button To switch on the UPS press and...

Page 14: ...lay reverts to showing the UPS status after a few seconds Display Description O P VOLT xxx xV Output voltage V O P FREQ xx x HZ Output frequency Hz I P VOLT xxx xV Input voltage V I P FREQ xx x HZ Inp...

Page 15: ...ut frequency Free Run Set UPS sets and maintains frequency at nominal value itself ON OFF Bypass on in autonomous mode only shown if free run mode is active Bypass disable When activated the UPS can s...

Page 16: ...ve power at output cos 1 for external battery in the technical data Backup times may be extended by using external battery units in addition to the integrated battery units Connection is established b...

Page 17: ...every 6 months at least 8 1 2 Function test The UPS should be tested for correct operation every six months You may use a test load to do so This will allow a more precise assessment of the UPS s cond...

Page 18: ...of backup Charger Failure Continuous tone Battery charger failure Request service Over Temperature Continuous tone Ambient temperature too high Check the UPS s cooling air flows for blockages reduce a...

Page 19: ...take back UPS units and batteries from the operator free of charge and recycle them accordingly Do not dispose of the equipment with regular household waste 10 Other technical documents We supply the...

Page 20: ...6 A Input power factor at 100 load 0 97 Bypass input Input voltage range adjustable 184 265 VAC Battery Number of battery cells JOVYTEC PE series 18 24 36 48 Number of battery blocks JOVYTEC PE series...

Page 21: ...m 425 mm 84 mm Weight w o integrated battery w o additional charger 10 0 kg 11 6 kg 17 2 kg 18 2 kg Weight w o integrated battery with additional charger 10 7 kg 12 3 kg 18 0 kg 19 0 kg Weight with in...

Page 22: ...short version only Depth Height 428 mm 425 mm 84 mm 428 mm 425 mm 84 mm Additional data Finish RAL 9005 Weight w o integrated battery 8 4 kg 12 2 kg 18 3 kg 18 3 kg Weight with integrated battery 24 3...

Reviews: