JOVYTEC PE / PME
100000004673
- 15 -
6.1.6
Configuration
ATTENTION:
The system should only be modified if said modifications are absolutely indispensable. If in doubt,
please consult your authorised dealer first.
Procedure:
To configure, press and hold the <FUNC> button for about 2 seconds.
Then press the <FUNC> button repeatedly until the desired setting (column 2) appears.
Then press <ENTER>: The current setting value appears.
Press <FUNC> repeatedly to select the desired value (column 4).
Press <ENTER> to confirm the setting.
When the display shows “Save ?”, press <ENTER> once more.
Note: If any button is not being pressed for a time, the display reverts to what it was showing previously and no
changes are adopted.
1. Designation
2. Text on display
3. Description
4. Options
available
Default value
Nominal output voltage
(version 220/230/240 V)
O/P V Setting
For selecting nominal output voltage
208V
220V
230V
240V
Nominal output voltage
(version 100/110/115/120 V)
O/P V Setting
For selecting nominal output voltage
100V
110V
115V
120V
127V
Input frequency tolerance window
I/P F Setting
For selecting tolerance range in which the UPS
matches output frequency
±2%
±5%
±7%
Bypass voltage tolerance window
I/P Bypass Set
For selecting tolerance range in which the UPS
may switch to bypass if necessary
+/-10%
+10% / -15%
+15% / -20%
Autonomous adjustment of output
frequency
Free Run Set
UPS sets and maintains frequency at nominal
value itself
ON
/ OFF
Bypass on in autonomous mode
(only shown if free-run mode is
active!)
Bypass disable
When activated, the UPS can switch to bypass
even without synchronising.
ON /
OFF
High-efficiency mode
HE Mode Set
For choosing between online mode and high-
efficiency mode (bypass mode) including setting
tolerance range
ON +/-10%
ON +/- 15%
OFF
Activate internal bypass*)
Manual Bypass
Force UPS to internal bypass
ON /
OFF
Output group controls
Outlet Setting
For setting the two output groups for the
consumers: both on/one on only/both off
1 ON & 2 ON
1 OFF & 2 ON
1 ON & 2 OFF
1 OFF & 2 OFF
Battery test
Battery Test
Battery quick test (approx. 5 seconds)
Test ?
Switch off alarm sound
Silence Set
Switches off the alarm sound
ON /
OFF
Configured
number
of
external
battery cases**)
Bat Cabinet Set
Sets number of external battery cases for
calculating backup time
0
/1/2
Alert to inverted supply grid
Sit Fault Set
Sounds an alarm if phase and neutral line have
been swapped over at input.
Disable
Enable
Language setting
Language
Language setting
English
Deutsch-German
Français-French
Espaňol-Spanish
Italian
Generator mode***)
Generator
For activating generator mode special function
ON/
OFF
RS-232 interface settings
RS232 Control
For setting RS-232 interface
Enable
Disable
*)
For servicing only; load is not supplied if grid fails while this function is active.
**)
Depends on backup time
***)
Every time you change this setting: leave UPS connected to grid, use ON/OFF to restart.